RC SERIES INSTALLATION MANUAL

Compressor Fixed On Delay Time

The Compressor Fixed On Delay Time will ensure that the 
compressor output (B02) is not enabled for (90) seconds after 
the control receives a call to start the compressor. This delay is 
adjustable from 30 – 300 seconds over a BAS or a MUI. If the 
control is in test mode the Compressor Fixed On Delay Timer will 
be shortened to 5 seconds.

Compressor Minimum On Delay

The compressor minimum on delay will ensure that the 
compressor output is enabled for a minimum of (2) minute each 
time the compressor output is enabled. This will apply in every 
instance except in the event the high pressure switch is tripped or 
emergency shutdown then the compressor output will be disable 
immediately.

Compressor Short Cycle Delay Time

The compressor short cycle time delay will ensure that the 
compressor output will not be enabled for a minimum of (5) 
minutes after it is disabled. This allows for the system refrigerant 
pressures to equalize after the compressor is disabled.

Heating Cycle

On a call for heating, the blower enable output and accessory 
output 2 will turn on immediately after the random start delay timer 
has been satisfied. If the compressor short cycle time delay has 
been satisfied, the compressor will turn on after the blower enable 
and accessory output 2 are on and the fixed compressor start 
delay timers have been satisfied.

Auxiliary heat output can be controlled over the BAS.

Set Point Control Mode

In set point control mode the reversing valve output will be 
disabled. As the temperature drops below the heating set 
point and begins to operate in the heating proportional band, 
the low capacity compressor output (BO-2) will be enabled. A 
PI loop in the programming of the control will determine when 
the full capacity compressor output (BO-4) is to be enabled. 
The compressor must be operating in low capacity for a 
minimum of 30 seconds before the full capacity compressor 
output can be enabled. During low capacity compressor 
operation the ECM2 blower will operate in medium speed and 
will operate in high speed when the compressor is operating 
at full capacity.

Thermostat Control Mode

In thermostat mode the compressor will be cycled based on 
Y1 and Y2 calls from a room thermostat.  When the control 
receives a Y1 command (BI-7) from the thermostat the 
low capacity compressor output (BO2) will be enabled and 
the ECM2 blower will operate in medium speed. When the 
control receives a Y2 command (BI-8) from the thermostat 
the full capacity compressor output will be enabled and the 
ECM2 blower will operate in high speed. During the heating 

cycle the reversing valve will be commanded into the off 
position.

Cooling Cycle

On a call for cooling, the blower enable output and accessory 
output 2 will turn on immediately after the random start delay timer 
has been satisfied. If the compressor short cycle time delay has 
been satisfied, the compressor will turn on after the blower enable 
and accessory output 2 are on and the fixed compressor start 
delay timers have been satisfied.

Set Point Control Mode

In set point control mode the reversing valve output will be 
enabled. As the temperature falls below the cooling set point 
and begins to operate in the cooling proportional band, the 
low capacity compressor output (BO-2) will be enabled. A PI 
loop in the programming of the control will determine when 
the full capacity compressor output (BO-4) is to be enabled. 
The compressor must be operating in low capacity for a 
minimum of 30 seconds before the full capacity compressor 
output can be enabled. During low capacity compressor 
operation the ECM2 blower will operate in medium speed and 
will operate in high speed when the compressor is operating 
at full capacity.

Thermostat Control Mode

In thermostat mode the compressor will be cycled based on 
Y1 and Y2 calls from a room thermostat.  When the control 
receives a Y1 command (BI-7) from the thermostat the 
low capacity compressor output (BO2) will be enabled and 
the ECM2 blower will operate in medium speed. When the 
control receives a Y2 command (BI-8) from the thermostat 
the full capacity compressor output will be enabled and the 
ECM2 blower will operate in high speed. During the cooling 
cycle the reversing valve will be commanded into the “ON” 
position.

ECM2 Blower Operation

Fan speeds will be selected through the user interface or the 
facility management system. There will be a total of 12 speeds 
selectable with only three being selected at any one time. The 
lowest numbered speed selection set to ON will select the low-
speed fan setting, the middle selection set to ON will select the 
medium-speed fan setting and the highest selection set to ON 
will select the high-speed fan setting. If all selections are set to 
OFF the software shall select speed setting 10 for low-speed, 
11 for medium-speed, and will select speed setting 12 for high 
speed.  If only one selection is set to ON, that selection will set the 
low-speed fan setting, the medium-speed setting will be 11, and 
the high-speed setting will be speed 12. The maximum low-speed 
setting will be speed 10 and the minimum high-speed setting will 
be speed 3. In addition there is a low limit setting in the software to 
prevent the ECM2 fan speed from being set below acceptable limits 
for each unit size.

Controls - FX10 cont.

Содержание RC Series

Страница 1: ...Installation Manual RC Series Geothermal Water Source Heat Pump R 410A Refrigerant 0 75 1 5 Tons Single Speed Installation Information Water Piping Connections Electrical Startup Procedures Troubleshooting Preventative Maintenance ...

Страница 2: ......

Страница 3: ...ing 17 Open Loop Ground Water Systems 18 Electrical Connections 19 Auxiliary Heat Ratings 19 Electrical Data 20 Fan Performance Table 20 Wiring Schematics 21 25 Controls 26 40 Startup Notes 41 Startup Checklist Unit Startup Steps 42 Operating Parameters 43 Operating Limits 43 Startup Troubleshooting Form 44 Pressure Drop 45 Preventive Maintenance 46 Replacement Procedures 46 ...

Страница 4: ...ation only w t stat control option 2 5 FX10 w Open N2 Com Card only w t stat control option 2 6 FX10 w Lonworks Com Card only w t stat control option 2 7 FX10 w BacNet Com Card only w t stat control option 2 Vintage A Current Non standard Option Details SS Standard Option Air Coil Insulation Option 1 FormiShield Extended Range 2 FormiShield Standard Range 3 No Coating Extended Range 4 No Coating S...

Страница 5: ...he packaging if necessary Units in question should also be internally inspected If any damage is noted the carrier should make the proper notation on the delivery receipt acknowledging the damage Water Piping The proper water flow must be provided to each unit whenever the unit operates To assure proper flow use pressure temperature ports to determine the flow rate These ports should be located at...

Страница 6: ... 3 124 7 29 8 10 9 09 12 15 18 F B G I J C E D A H FILTER BRACKET FILTER BRACKET RIGHT RETURN TOP FRONT LEFT RETURN DETAIL B TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAME SIDE AS GRILLE LID AS SHOWN DETAIL B TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAME SIDE AS GRILLE LID AS SHOWN B A REMOVE PLASTIC STRIP FROM BROKEN TAB AND REPLACE...

Страница 7: ... 4 124 7 29 8 10 9 09 12 15 18 REMOVE PLASTIC STRIP FROM BROKEN TAB AND REPLACE ON BROKEN EDGE OF LEG AS SHOWN H I J C F E A D G B RIGHT RETURN TOP FRONT LEFT RETURN DETAIL B TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAME SIDE AS GRILLE LID AS SHOWN DETAIL A TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAME SIDE AS GRILLE LID AS SHOWN RE...

Страница 8: ...0 12 6 29 1 9 2 35 0 6 1 2 5 54 1 11 8 4 3 cm 139 7 32 0 73 9 23 4 88 9 15 6 6 4 137 4 29 8 10 9 09 12 15 18 FILTER BRACKET FILTER BRACKET A D E C H I J F B G A B RIGHT RETURN TOP FRONT LEFT RETURN DETAIL B TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAME SIDE AS GRILLE LID AS SHOWN DETAIL A TWIST EXTENDED TAB BACK AND FORTH UNTIL TAB BREAKS OFF ONLY BREAK OFF TAB SAM...

Страница 9: ...DE NORMAL BOILERLESS SWITCH OPTIONAL FAN OPTION SWITCH OPTIONAL BACK PLATE REQUIRED FOR DAMPER INSTALLATION OUTSIDE AIR DAMPER OPTION FIELD INSTALLED LOW VOLTAGE TERMINALS FX10 REMOTE WALL STAT OPTIONS ONLY OPTIONAL FUSED NON FUSED DISCONNECT OPTIONAL BALL VALVES OPTIONAL HOSE KITS CONDENSATE DRAIN CONNECTION FILTER HANDY BOX Dimensional Data Right Return Controls Detail ...

Страница 10: ... 65 65 2 19 83 50 4 1 64 4 2 12 03 30 6 0 66 1 7 2 75 7 0 5 5 14 0 DAMPER OPENING Models 09 12 BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL 42 88 108 9 34 0 86 4 1 5 3 8 1 5 3 8 4 32 11 0 8 88 22 6 FILTER CONTROL PANEL 25 25 64 1 0 86 2 2 11 75 29 8 1 0 2 5 12 0 30 5 4 5 11 4 2 0 5 1 20 6 52 3 19 5 49 5 CONDENSATE DRAIN CONNECTION WATER OUT 1 2 FPT WATER IN 1 2 FPT OPTIONAL BACK PLATE COMPRESSOR AC...

Страница 11: ...CONNECTION FILTER HANDY BOX OPTIONAL ELECTRIC HEAT OPTIONAL BACK PLATE REQUIRED FOR DAMPER INSTALLATION OUTSIDE AIR DAMPER OPTION FIELD INSTALLED CONTROL PANEL REMOVE FOR ACCESS TO CONTROL BOX DAMPER ON OFF SWITCH COMPRESSOR ACCESS PANEL REMOVED FOR CLARITY BOTH SIDES ELECTRIC HEAT MODE NORMAL BOILERLESS SWITCH OPTIONAL FAN OPTION SWITCH Dimensional Data Left Return Controls Detail ...

Страница 12: ... COMPRESSOR ACCESS PANEL DAMPER OPENING 43 37 110 2 1 62 4 1 25 65 65 1 19 83 50 4 Models 09 12 8 88 22 6 34 0 86 4 1 50 3 8 1 50 3 8 4 32 11 0 42 88 108 9 BLOWER ACCESS PANEL COMPRESSOR ACCESS PANEL FILTER CONTROL PANEL 1 00 2 5 11 75 26 2 4 5 11 4 0 86 2 2 2 0 5 1 25 25 64 1 20 6 52 3 19 5 49 5 12 0 30 5 CONDENSATE DRAIN CONNECTION WATER OUT 1 2 FPT WATER IN 1 2 FPT 33 0 83 8 13 90 35 3 11 78 29...

Страница 13: ...hims used Position backplate in desired equipment location To further reduce the operating sound level of the unit 1 8 inch thick rubber matting may be placed under the chassis to eliminate vibration on hard flooring surfaces Make sure back plate is level Mark and cut floor or wall penetrations for electrical wiring water and condensate piping Optional Electrical Disconnect and Motorized Outside A...

Страница 14: ...tion system The supply and return water piping should be run through the wall or floor penetration and terminate with a ball valve The piping material used must comply with all local codes Refer to System Cleaning and Flushing procedures Pipe Locations Figure 2 CONSOLE CABINET CONSOLE CHASSIS CONDENSATE DRAIN LOCATION WATER CONNECTIONS TARGET AREA FOR WALL PENETRATION FUSED ELECTRICAL DISCONNECT O...

Страница 15: ...ould be installed on both the supply and return water lines of the unit Flow control valves should be installed on the water discharge line It is recommended that P T ports be installed on the supply and return water lines Step 9 Set Unit Controls Locate the continuous fan cycle fan switch within the electrical compartment of the chassis and set to desired position Remote wall thermostat units do ...

Страница 16: ...et repositioning pieces 4 1 2 and 3 into the locations directly opposite the original positions Secure by replacing mounting brackets Note Be sure that louvers on the grille assembly are facing the proper direction when replacing the grille section Replace grille frame assembly into cabinet and secure by replacing 5 mounting brackets Replace cabinet by sliding it down over the top of the chassis 6...

Страница 17: ...ct the system from dirty water conditions Dirty water will result in system wide degradation of performance and solids may clog valves strainers flow regulators etc Additionally the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure In boiler tower application set the loop control panel set points to desired temperatures Supply power to all...

Страница 18: ...iance in your area Note For open loop groundwater systems or systems that do not contain an antifreeze solution set SW1 Switch 2 to the WELL posi tion Refer to the Dip Switch Field Selection table Slow opening closing solenoid valves type VM are recommended to eliminate water hammer Water Quality In ground water situations where scaling could be heavy or where biological growth such as iron bacter...

Страница 19: ...X2 X1 W2 Field Connections Unit Connections 24 VAC COMMON COMPRESSOR REVERSING VALVE FAN LOCKOUT SIGNAL SHUTDOWN NIGHT SETBACK LOAD SHED Requires common connections or 24 VAC for activation Red Black Yellow Orange Green Brown Blue Violet Pink Figure 5 Model Rated Voltage Voltage Min Max Heater Element Watts Fan Motor FLA Heater Element FLA Total Unit FLA Min Circuit Amp Max Fuse Brkr 09 12 208 60 ...

Страница 20: ...500 fpm by 0 16 in wg Electrical Data Model Rated Voltage Voltage Min Max Compressor Fan Motor FLA Total Unit FLA Min Circ Amp Max Fuse HACR MCC RLA LRA 09 208 230 60 1 197 253 6 4 4 1 21 0 0 50 4 6 5 6 10 265 60 1 238 292 na 4 3 22 0 0 50 4 8 5 9 10 12 208 230 60 1 197 253 7 7 4 9 25 0 0 50 5 4 6 7 10 265 60 1 238 292 na 5 3 22 0 0 50 5 8 7 1 10 15 208 230 60 1 197 253 9 2 5 9 29 0 0 69 6 6 8 1 1...

Страница 21: ...ite 20 Orange 14 Orange 21 Black 29 Red 30 Black Black 12 White 18 Red 11 Red 19 Red 17 24 V Accessory 24VAC Shutdown Red 15 Red 16 NOTE 1 T ST CC Compressor Contactor HP High Pressure Switch LP Low Pressure Switch RV Reversing Valve Coil ST Entering Air Temperature Sensor RB Blower Relay Black Black Red 11 Black 12 Red 17 Red 19 Black 25 White 28 Black 31 Red 32 Brown 26 RB 4 2 5 Red RV DT ON OFF...

Страница 22: ...ack 27 RB 4 2 5 Red EH T2 T1 L2 White White L1 EH Normal RV DT ON OFF Damper Sw Damper Motor D Fan Mode Sw 4 5 2 E1 E1 AQ Blk Wht 24 Blk Wht 23 Black 22 White 18 Blue T6 NOTE 2 3 1 RB 3 1 Black 37 Blue 38 Blue Wht 36 Blue Wht 35 White 34 Blue T6 FS Yellow 44 Yellow 44 Brown 43 Yellow 13 Blue Tan 41 Blue 40 White 28 Blue 40 Brown 3 Tan 41 Brown 26 Green 00 Red 39 Gray 42 NOTE 3 NOTE 4 Violet 4 Viol...

Страница 23: ...ON Current fault or Output display mode activated Normal Standard timings Well Open loop freeze sensing setting 30 F Normal Unit status display Normal Standard thermostat operation Normal Standard delay on call from compressor used Refer to LED Display Mode table for position of SW1 4 and SW2 LogicBoard DIP Switch Settings Normal Control Timing Table Blower offdelay Compressor on delay Shortcycle ...

Страница 24: ...g information for specific thermostat hookup instructions Red Black 25 RB Gray 42 White 28 Black 29 Red 30 Damper Motor Off On DAMPER MODE DT D Blue Wht 35 MV Black 31 Red 32 Handi Box Ground Lug Unit Power Supply 208 230 60 1or 265 277 60 1 G C R Y1 O G L S Terminal Board X2 X1 W1 Red Bl ack Yellow Orange Brown Green NOTE 2 Violet Pink Bl ue 1 3 4 2 NOTE 1 ES Emergency Shutdown Black White Black ...

Страница 25: ...reeze protection Field Zone Sensor Wiring 3 Acc 1 output is cycled with the compressor 4 Acc 2 output is cycled with the fan 5 R C Y1 O and G inputs are for use with a wall mounted thermostat A23 A13 A11 A21 A12 A25 A22 Open Jumper Closed Jumper 2 TB R C Y1 O G L X1 X2 24VAC 24V COM Alarm Acc 1 Acc2 Fan Rev Valve Comp SS AIC RS SC TO Setpoint Shift AI Com Room Sensor Sensor Com Temp Occ EHC T2 T1 ...

Страница 26: ...cts Optional Medium User Interface MUI can be used as a field service tool Standalone Unit Mounted Digital Dial Sensor Remote Mounted Standard Thermostat Remote Mounted Sensor FX10 w N2 FX10 Control functions as both unitary heat pump control and DDC communica tion therefore detail operational and fault information is available to BAS Other features are same as FX10 with addition of Johnson Contro...

Страница 27: ...is disabled Optional Versatec Microprocessor Control Features The Versatec microprocessor board provides control of the entire unit as well as outputs for status modes faults and diagnostics The control system is a microprocessor based control board that is located in the unit control box This feature is available for either unit mounted controls or optional remote wall mounted thermostat A 9 pin ...

Страница 28: ...fault recognition delay 30 seconds Low pressure fault bypass delay 2 minutes Freeze sensing fault bypass delay 2 minutes Power on delay 5 minutes Normal Control Timing Operational Logic Blower off delay 5 seconds Compressor on delay 2 seconds Short cycle delay 15 seconds Miniumum compressor on time 5 seconds except for fault condition High pressure fault recognition delay Less than 1 second low pr...

Страница 29: ...er Coil Low Temperature Freeze Sensing Condensate overflow sensing Lockout mode control Emergency shutdown mode Random start and short cycle protection Short Cycle Protection Allows a minimum compressor off time of four minutes and a minimum on time of two minutes Random Start A delay of 1 to 120 seconds is generated after each power up to prevent simultaneous startup of all units within a buildin...

Страница 30: ... on from a BAS as needed An alarm history can be viewed through the MUI and will be held in memory until the unit is power cycled Relative humidity can be read by a 0 5VDC humidity sensor that is displayed over the network If you are using an ECM fan motor the control can enable dehumidification mode based on a set point in the control The dehumidification set point itself can also be changed over...

Страница 31: ...ow Temp Limit fault High Pressure BI 11 The high pressure switch shall be a normally closed NC switch that monitors the systems refrigerant pressure If the input senses the high pressure switch is open it must disable the compressor output immediately and count the fault The compressor minimum on time does not apply if the high pressure switch opens The compressor will not restart until the compre...

Страница 32: ... ECM2 blower will operate in high speed During the heating cycle the reversing valve will be commanded into the off position Cooling Cycle On a call for cooling the blower enable output and accessory output 2 will turn on immediately after the random start delay timer has been satisfied If the compressor short cycle time delay has been satisfied the compressor will turn on after the blower enable ...

Страница 33: ...ng Limit Set Point BI 5 The water coil low temperature freeze sensing limit set point input allows you to adjust the water coil low temperature freeze sensing limit set point AI 5 When the jumper is installed on BI 5 Wire 24 the water coil low temperature freeze sensing limit set point is factory set for 30 F When the jumper on BI 5 Wire 24 is removed the water coil low temperature freeze sensing ...

Страница 34: ...Water to Air Welcome Info Status Temps Outputs Settings Maint Alarms Alm History PROFXENV XX 3 8 07 Info Run Mode Auto Eff Occup y Occ Y1 Input OFF Y2 Input OFF G Input OFF O Input OFF Occ Input Occ Temp Occ Inp OFF Condensate NML Emg Input Run Lo Press ON Hi Press ON Rndm Tmr 0 BI 4 Input OFF Status Zone Temp 77 2 ºF Dis Air Temp 51 0 ºF Eff Clg Setpt 70 0 F Eff Htg Setpt 66 0 F Water Coil 77 8 F...

Страница 35: ...Bad Sensor 0 Alm History NOTE This FX10 application implements an alarm history which is reset only by cycling power This history shows on the Alm History page Any alarm showing 4 events has occurred more than 4 times Alarm lock outs are reset by cycling power by pressing the ESC and Return keys simultaneously for a minimum of 15 seconds or by commanding the nviAlarmReset over the BAS network Test...

Страница 36: ...ating Freeze Sensing Temperature Value Read Only ADF 40 nvoHtgFrzSetpt Heating Freeze Sensing Temperature Setpoint Value Read Only ADF 41 nvoAlarms Alarms Enumerated 0 no alarms 1 condensate alarm 2 Compressor Hi Discharge Pressure alarm 3 Compressor low Suction Pressure alarm 4 Freeze sensing alarm 8 Faulty Freeze Sensor alarm 9 Loss of Charge Read Only ADF 62 nvoPWMOut ECM PWM Control signal val...

Страница 37: ... Compressor low Suction Pressure alarm 4 Freeze sensing alarm 8 Faulty Freeze Sensor alarm 9 Loss of Charge Read Only nvoPWMOut SNVT_volt 44 ECM PWM Control signal value Read Only nvoECMOvrd SNVT_volt 44 ECM PWM Control signal Override Read Write nvoHumidity SNVT_volt 44 Space Humidity value Read Only nviAO2 SNVT_lev_percent 81 Spare PWM Output AO2 Command Write nvoAO2 SNVT_lev_percent 81 Spare PW...

Страница 38: ...m 9 Loss of Charge Read Only Analog Input 0 8 Present_Value 85 WFI ECM Cmd Output Present_Value ECM PWM Control signal value Read Only Analog Output 1 2 Present_Value 85 WFI ECM Fan Ovrd Present_Value ECM PWM Control signal Override Read Write Analog Input 0 5 Present_Value 85 WFI Space Humidity Present_Value Space Humidity value Read Only Analog Output 1 3 Present_Value 85 WFI AO2 Override Presen...

Страница 39: ...k to send space temperature values to the heat pump controller volatile these will supersede any temperature sensor connected to the space temperature Analog Input Analog Value Type 2 2 1 Occupied Cool Write Cooling setpoint in Occupied mode 2 2 Unoccupied Cool Write Cooling setpoint in Unoccupied mode 2 3 Occupied Heat Write Heating setpoint in Occupied mode 2 4 Unoccupied Heat Write Heating setp...

Страница 40: ...and equivalent of a thermostatic G call 14 3 Compressor Cmd Y1 Write allows a network command equivalent of a thermostatic Y1 call 14 4 Compressor Cmd Y2 Write allows a network command equivalent of a thermostatic Y2 call 14 5 Reversing Vlv Cmd O Write allows a network command equivalent of a thermostatic O call 14 6 Emergency Overide Write provide rapid shutdown of the heatpump for fire etc 1 Nor...

Страница 41: ... in five models with equip ment rated fuses to provide additional circuit protection The fuses are panel mounted to allow easy inspection and removal without removing the cover on the disconnect CFD 10 10 amp rated fuse CFD 12 12 amp rated fuse CFD 15 15 amp rated fuse CFD 20 20 amp rated fuse CFD 25 25 amp rated fuse Motorized Outside Air Damper A field installed motorized outside air damper is a...

Страница 42: ...tpoint must be set below room temperature 3 Be sure that the compressor and water control valve or loop pump s are activated 4 Verify that the water flow rate is correct by measuring the pressure drop through the heat exchanger using the P T plugs and comparing to unit capacity data in specification catalog 5 Check the temperature of both the supply and discharge water Refer to Unit Operating Para...

Страница 43: ...ormance based on entering air temperatures of 80º F DB 67º F WB Heating performance based on entering air temperature of 70º F DB Operating Limits F C F C Air Limits Min Ambient Air 45 7 2 45 7 2 Rated Ambient Air 80 26 7 70 21 1 Max Ambient Air 100 37 8 85 29 4 Min Entering Air 50 10 0 40 4 4 Rated Entering Air db wb 80 6 66 2 27 19 68 20 0 Max Entering Air db wb 110 83 43 28 3 80 26 7 Water Limi...

Страница 44: ...for water antifreeze x T Note DO NOT hook up pressure gauges unless there appears to be a performance problem Line Voltage Loop Open Unit Amp Draw Closed COAX SOURCE HEATING CYCLE ANALYSIS EXPANSION VALVE F AIR COIL F F PSI PSI BRINE IN BRINE OUT COMPRESSOR DISCHARGE SUCTION Subcooling Superheat REVERSING VALVE PSI F SAT F PSI SAT F F F LIQUID LINE F Line Voltage Loop Open Unit Amp Draw Closed DEA...

Страница 45: ... 1 2 1 0 0 9 0 8 0 7 0 6 1 8 2 3 2 2 2 0 1 9 1 8 2 5 3 8 3 7 3 5 3 3 3 1 12 1 5 0 9 0 8 0 7 0 6 0 5 2 3 1 7 1 5 1 4 1 3 1 1 3 5 3 0 2 7 2 5 2 4 2 2 15 2 0 1 7 1 6 1 5 1 4 1 3 3 0 3 3 3 2 3 0 2 9 2 8 4 5 5 7 5 5 5 3 5 1 4 9 18 3 0 1 7 1 6 1 5 1 4 1 3 4 0 4 1 4 0 3 9 3 7 3 6 5 5 7 9 7 6 7 4 7 2 6 9 3 4 08 ...

Страница 46: ...re Note On open loop systems if the installation is in an area with a known high mineral content 125 PPM or greater in the water it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly Should periodic coil cleaning be necessary use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines Generally t...

Страница 47: ......

Страница 48: ...Product RC Series Type Geothermal Water Source Heat Pump Size 0 75 1 5 Tons Document Type Installation Manual Part Number 146 00 NOM4 Release Date 02 10 ...

Отзывы: