IV. Venting
A. General Guidelines - B. CPVC/PVC Venting (continued)
Figure 7: Direct Vent - Vertical Terminations
Extend vent/combustion air piping to maintain minimum vertical (‘X’) and minimum horizontal (‘Y’) distance
of 12 in. (300 mm) [18 in. (460 mm) Canada] from roof surface. Allow additional vertical (‘X’) distance for
expected snow accumulation.
itself. If these objects are subject to damage by
flue gas condensate, they should be moved or
protected.
n. If possible, install the vent and combustion air
terminals on a wall away from the prevailing
wind. Reliable operation of this boiler cannot be
guaranteed if terminals are subjected to winds in
excess of 40 mph (64 km/hr).
o. Do not locate combustion air terminal in areas
that might contain combustion air contaminates,
such as near swimming pools.
p. For multiple boiler installations with horizontal
wall terminals, maintain minimum 12 in.
(300 mm) horizontal distance between adjacent
boiler vent terminals. Maintaining greater
spacing is recommended to avoid frost damage
to building surfaces where vent terminations are
placed.
q. For multiple boiler installations with vertical
roof terminals, maintain minimum 12 in.
(300 mm) horizontal distance between adjacent
boiler vent terminals.
B. CPVC/PVC Venting
WARNING
Asphyxiation Hazard. Failure to follow
these instructions could cause products of
combustion to enter the building, resulting
in severe property damage, personal injury,
or death.
Use all CPVC vent components (supplied
with boiler) for near-boiler vent piping before
transitioning to Schedule 40 PVC pipe
(ASTM 2665) components for remainder of
vent system.
Use CPVC vent components within any
interior space where air cannot circulate
freely, including through vertical or
horizontal chase ways, inside a stud wall, in
closets, and through wall penetrations.
The use of cellular core PVC (ASTM
F891), cellular core CPVC or Radel
(polyphenolsulfone) is prohibited.
All condensate that forms in the vent must
be able to drain back to the boiler.
Figure 8: Direct Vent - Vertical Terminations
with Sloped Roof
Содержание APEX
Страница 6: ...6 I Product Description Specifications and Dimensional Data continued Figure 1A Apex Model APX425 ...
Страница 7: ...7 Figure 1B Apex Model APX525 I Product Description Specifications and Dimensional Data continued ...
Страница 9: ...9 I Product Description Specifications and Dimensional Data continued Figure 1D Apex Model APX825 ...
Страница 57: ...57 VIII Electrical continued Figure 26 Ladder Diagram ...
Страница 58: ...58 VIII Electrical continued ...
Страница 59: ...59 Figure 27 Wiring Connections Diagram VIII Electrical continued ...
Страница 68: ...68 IX System Start up continued Apex Series Operating Instructions Figure 34 Operating Instructions ...
Страница 105: ...105 ...
Страница 109: ...109 XIII Repair Parts continued APX625 APX725 and APX825 APX825 shown ...
Страница 112: ...112 XIII Repair Parts continued APX425 and APX525 ...
Страница 114: ...114 XIII Repair Parts continued APX625 APX725 and APX825 ...
Страница 122: ...122 ...
Страница 123: ...123 ...