background image

15

SKP 20

Alar

m C

ode

Name of A

lar

m

Not

es

Dig

ital/A

nalogue

Alar

m t

ype

Sanitar

y w

ater v

alv

e

Sanitar

y w

ater hea

ter

Compr

essors

Ex

ter

nal e

xchanger fan

Recir

cula

tion fan

Int

ernal cir

cuit pump

Ex

ter

nal cir

cuit pump

Int

ernal e

xchanger hea

ters

Ex

ter

nal e

xchanger hea

ters

Output Auxiliar

y

Boiler

E047

LAN communication absent

AUTO

E048

Anti-legionnaires alarm

AUTO

E050

Primary exchanger electric heater 1 thermal switch

D

AUTO

OFF

RES.1

E051

Primary exchanger electric heater 2 thermal switch

D

AUTO

OFF

RES.2

E056

Auxiliary output thermal switch

D

AUTO

OFF

E060

Primary exchanger water or air input temperature 

probe faulty

AUTO

See Probe Errors Table

E061

Primary exchanger water or air output temperature 

probe faulty, and/or Circuit 1 primary exchanger 

water outlet temperature probe faulty,

and/or Circuit 2 primary exchanger

water outlet temperature probe faulty

AUTO

See Probe Errors Table

E062

Circuit 1 external exchanger temperature

probe faulty, and/or Circuit 2 external

exchanger temperature probe faulty

AUTO

See Probe Errors Table

E063

Faulty disposable exchanger water or air input 

temperature probe

AUTO

See Probe Errors Table

E064

Faulty disposable exchanger water or air output 

temperature probe

AUTO

See Probe Errors Table

E065

Faulty ambient temperature probe

AUTO

See Probe Errors Table

E066

Sanitary water temperature probe faulty

AUTO

See Probe Errors Table

E067

Faulty display probe

(temperature / pressure)

AUTO

See Probe Errors Table

E068

Faulty external temperature probe

AUTO

E069

Faulty circuit 1 high pressure transducer or

Faulty circuit 2 high pressure transducer

AUTO

See Probe Errors Table

E070

Faulty circuit 1 low pressure transducer

Faulty circuit 2 low pressure transducer

AUTO

E071

Faulty compressor 1 discharge temperature probe

AUTO

E073

Faulty dynamic setpoint input

AUTO

E074

Faulty primary heat exchanger transducer

circuit 1, and/or Faulty primary heat

exchanger transducer circuit 2

AUTO

See Probe Errors Table

E075

Faulty disposable exchanger transducer

circuit 1, and/or Faulty disposable

exchanger transducer circuit 2

AUTO

See Probe Errors Table

E080

Configuration error

AUTO

OFF

OFF

E081

Compressor operating hours exceeded (*)

CMP

Manual

E085

Primary circuit pump operating hours exceeded (*)

PUMP

Manual

E086

External circuit pump operating hours exceeded (*)

PUMP

Manual

E090

Alarm log full warning

Manual

Содержание ENERGY FLEX SKP 20

Страница 1: ...SKP 20 LCDTerminals User manual for ENERGY FLEX english ...

Страница 2: ...SKP 20 ...

Страница 3: ...tpoweron 6 1 3 1 Accesstofolders menustructure 6 1 3 2 MaindisplayMenu 6 1 3 3 OperatingMode Menu 7 1 3 4 Settingtheclock CL 7 1 3 5 AlarmDisplay AL 8 1 3 6 Exampleofhowtosetthesetpoint SP 8 1 3 7 Resetcompressor pumptime 9 1 3 8 Parameters folderPAr 9 1 3 9 Settingapassword Par PASSfolder 10 1 3 10 Alarmevents Par EUfolder 10 DIAGNOSTICS 2 1 Alarms 12 2 1 1 Automaticreset 12 2 1 2 Manualreset 12 ...

Страница 4: ...d with utilities are all configurable From the factory device is set to the table Key Press once press and release Longpress pressandholdforabout3seconds 1 Increaseavalue Gotonextlabel See also F1 Activate manual defrost See the Functions menu folder FnC 2 Decreaseavalue Gotopreviouslabel See also F3 Machine active OFF OFF machine active See Local On OFF section See also Functions menu FnC folder ...

Страница 5: ...ICON 2 Manual defrost Icons are associated with menu navigation and manual defrost The factory settings of the controller are listed in the table 1 1 5 DoubleLCD Whichwewillrefertoasfollows The double display has 26 icons States and operating modes 9 icons o Browse menu manual defrost 2 icons Values and units of measure 4 icons Utilities 7 icons Fans 4 icons Read outs can have up to Display A 4 di...

Страница 6: ...NU label Parameters PAr CL CL00 CF CF01 AL ALOO Functions FnC dEF tA St OFF ON CC UL dL Fr EUr Password PASS EU EU When Energy SKW22 L is powered on for the first time a lamp test is carried out to check its state and operation The LampTest lasts for just a few seconds During this short time all icons and digits flash at the same time After the lamp test the following are displayed depending on th...

Страница 7: ... press the set key to confirm You will be automatically returned to the preconfigured main display In this case AiL1 with a value of 7 5 C For example let s say you want to change from StbY to COOL mode To change operating mode press and hold the esc key for at least 2 seconds A blinking menu will open containing the values StbY standby HEAt heat and COOL cool that you can scroll using the DOWN ke...

Страница 8: ...roceed in the same way by first changing the device s mode from COOL to HEAT See Operating Mode Menu chapter To change the setpoint on your machine press the UP or DOWN key in the main display Label Ai appears on the display Use the UP and DOWN keys to scroll the other labels until you find the SP label Press the set key to open the SP menu The first display will be COOL mode and then scrolling wi...

Страница 9: ... key to change the value of the parameter CL01 in this case Press the up and down keys to change the value of the parameter CL01 in this case On selecting a value press the set key To exit this display and return to the previous level press the esc key N B pressing the set key confirms the modified value pressing the esc key returns you to the previous level without saving the new value entered Ex...

Страница 10: ...8 in this example Alarm start date 20 May in this example Alarm stop time HO alarm still active in this case Alarm stop date dO alarm still active in this case Type of alarm tY automatic AUtO or alternatively manual ManU To view the PASS folder in the main display press the Esc and Set keys at the same time esc set Pressing the two keys will open the menu containing the list of folders Use the up ...

Страница 11: ...11 SKP 20 ...

Страница 12: ...A 4 Not present Not present Not present AL12 Alarm code Name of alarm Bypass activation event Bypass time Automatic alarm activation time Manual alarm activation time Exit alarm deactivation time Number of interventions per sample time E006 NOTA 4 Circuit 2 low pressure alarm Circuit compressor activated or reversal of 4 way valve NOTE 1 NOTE 4 AL11 NOTA 4 Not present Not present Not present AL12 ...

Страница 13: ...ue lowpressure alarm Acircuit1 compressor isswitchedon orreversalof the4 way valve AL43 AL44 AL45 Notpresent A46 Circuit1 lowpressure probe E008 Circuit2 analogue lowpressure alarm Acircuit2 compressor isswitchedon orreversalof the4 way valve AL43 AL44 AL45 Notpresent A46 Circuit2 lowpressure probe E030 Primarycircuit antifreeze On Off localor remote input inheatmode NOTE2 AL50 AL51 NOTA3 AL52 Not...

Страница 14: ... CMP4 D Events OFFCOMP4 E015 Compressor1oilpressureswitch CMP1 D Events OFFCOMP1 E016 Compressor2oilpressureswitch CMP2 D Events OFFCOMP2 E017 Compressor3oilpressureswitch CMP3 D Events OFFCOMP3 E018 Compressor4oilpressureswitch CMP4 D Events OFFCOMP4 E020 Primarycircuitflowswitch D Time OFFformanual resetalarm OFF OFF OFFfor manual reset alarm OFF OFF E021 Primarycircuitpump1thermalswitch D Event...

Страница 15: ...aultydisposableexchangerwaterorairinput temperatureprobe AUTO SeeProbeErrorsTable E064 Faultydisposableexchangerwaterorairoutput temperatureprobe AUTO SeeProbeErrorsTable E065 Faultyambienttemperatureprobe AUTO SeeProbeErrorsTable E066 Sanitarywatertemperatureprobefaulty AUTO SeeProbeErrorsTable E067 Faultydisplayprobe temperature pressure AUTO SeeProbeErrorsTable E068 Faultyexternaltemperaturepro...

Страница 16: ...Serie SKP20 Issue Supersedese 02 15 Catalogue M 204b The data indicated in this manual is purely indicative The manufacturer reserves the right to modify the data whenever it is considered necessary ...

Отзывы: