Installation-, Operating-, Maintenance-Manual, Spare Part List
BCR05
AGT-PSG GmbH & Co.KG
Errors and printing mistakes excepted
Page 12
Translation - Manual BCR05 Rev. 06/2017
Assembly and Installation
Electrical Supply Line
The electrical supply line needs to be applied to the rail-mounted terminals in the shielded
enclosure “Advanced Security” (X1:04-05-06, notice circuit diagram).
Dismantle the right side panel of the cooler. Lay the electrical supply line through one of the
cable feedthroughs at the side-panel or back-panel of the cooler. Use a suitable cable gland
type M20x1,5. Dismantle the cover plate of the shielded enclosure “Advanced Security” (gray
polyester box). Lay the line through one of the free cable feedthroughs at the bottom of the
shielded enclosure. Therefore only use the pre-mounted cable gland. Apply the electrical supply
line to the corresponding rail-mounted terminals. Remount accurately all dismantled
components.
Right side panel
Cable feedthroughs
Shielded enclosure “Advanced Security”
Remote Monitoring Connection
The device has a remote monitoring option, i.e. a floating collective fault notification. The
remote monitoring line needs to be applied to the rail-mounted terminals in the shielded
enclosure “Advanced Security” (X1:01-02-03, notice circuit diagram).
Proceed with the installation according to the instructions for installing the electrical supply line.
WARNING! Overcharge! Maximum rated load for the remote monitoring connection is 250V,
50Hz, 40VA.