3.
FLAME FAILURE-RECYCLE MODE
–
With the “Recycle After Loss of Flame” option, upon loss of flame, the solenoid gas valve is
de-energized and the control proceeds to inter-purge before attempting to relight the flame.
–
Multi-try models permit three tries for ignition including inter-purges. If the burner relights, normal
operation resumes.
–
If the burner does not relight, the control will enter lockout.
•
Lockout Recovery:
–
Recovery from lock-out requires a manual reset by either resetting the thermostat, or removing 120 VAC
for a period of 5 seconds.