Model 5500 COLLECT
an
DRAIN
®
Owner’s Manual
System Supply Valve
Float Switch
Heating Element
“Test/Reset” Button
Drain Button
Alarm Light
System Drain Valve
Lower Pipe Nipple
Quick Reference Guide
LAMPS
INDICATES
Power
Unit is on.
Collect
Unit is collecting condensate. The supply valve is open and the drain valve is closed.
Drain
Unit is draining condensate. The supply valve is closed and the drain valve is open.
Auto
The automatic mode is on. Unit will automatically drain when full of condensate.
OPERATION
PRESS
Drain Condensate
Drain button for one (1) second or press remote drain button.
Test Electronics
Test/Reset button for one (1) second to verify lamps, main alarm, and dry auxiliary
contacts are functioning.
Auto On/Off
Test/Reset button four (4) times quickly to turn on and off the automatic drain mode.
Reset Lamp Flash
Test/Reset button for one (1) second.
Reset System
Test/Reset button for five (5) seconds will reboot the system and return to collect state.
Drain Override
Drain and Test/Reset buttons simultaneously for three (3) seconds.
WARNING: Use this ONLY when servicing the sprinkler systems and system has been
taken offline. Otherwise, this will fully open the auxiliary drain causing the sprinkler
system to activate.
ALARMS
INDICATES
Main Alarm/Dry Contacts,
ONLY
If Auto Drain Mode is not activated:
Condensate is full.
If Auto Drain Mode is active:
System is actively draining.
Collect Lamp, Single Flash
Malfunction with supply valve. Valve did not fully open or close during last cycle.
Drain Lamp, Single Flash
Malfunction with drain valve. Valve did not fully open or close during last cycle.
Drain Lamp, Double Flash
Malfunction, the level switch failed to reset during last drain cycle. The collection
pipe is still full of condensate.
Power Lamp, Single Flash
Malfunction, heater has been continuously operating for at least two (2) hours.
Power Lamp, Double Flash
An auto drain cycle has been performed.