Model 5500 COLLECT

an

DRAIN

®

 Owner’s Manual

System Supply Valve

Float Switch

Heating Element

“Test/Reset” Button

Drain Button

Alarm Light

System Drain Valve

Lower Pipe Nipple

Quick Reference Guide

LAMPS

INDICATES

Power

Unit is on.

Collect

Unit is collecting condensate. The supply valve is open and the drain valve is closed.

Drain

Unit is draining condensate. The supply valve is closed and the drain valve is open.

Auto

The automatic mode is on. Unit will automatically drain when full of condensate.

OPERATION

PRESS

Drain Condensate

Drain button for one (1) second or press remote drain button.

Test Electronics

Test/Reset button for one (1) second to verify lamps, main alarm, and dry auxiliary 
contacts are functioning.

Auto On/Off

Test/Reset button four (4) times quickly to turn on and off the automatic drain mode.

Reset Lamp Flash

Test/Reset button for one (1) second.

Reset System

Test/Reset button for five (5) seconds will reboot the system and return to collect state.

Drain Override

Drain and Test/Reset buttons simultaneously for three (3) seconds.
WARNING: Use this ONLY when servicing the sprinkler systems and system has been 
taken offline. Otherwise, this will fully open the auxiliary drain causing the sprinkler 
system to activate.

ALARMS

INDICATES

Main Alarm/Dry Contacts, 
ONLY

If Auto Drain Mode is not activated:

 Condensate is full.

If Auto Drain Mode is active:

 System is actively draining.

Collect Lamp, Single Flash

Malfunction with supply valve. Valve did not fully open or close during last cycle.

Drain Lamp, Single Flash

Malfunction with drain valve. Valve did not fully open or close during last cycle.

Drain Lamp, Double Flash

Malfunction, the level switch failed to reset during last drain cycle. The collection 
pipe is still full of condensate.

Power Lamp, Single Flash

Malfunction, heater has been continuously operating for at least two (2) hours.

Power Lamp, Double Flash

An auto drain cycle has been performed.

Содержание COLLECT anDRAIN 5500

Страница 1: ...1 Model 5500 Owner s Manual INST 5500 8 20 AGF Manufacturing Inc...

Страница 2: ...f typical collectors The Model 5500 maintains a comfortable temperature above freezing while minimizing power consumption AGF Manufacturing Inc 100 Quaker Lane Malvern PA 19355 www agfmfg com AGF Manu...

Страница 3: ...mp Flash Test Reset button for one 1 second Reset System Test Reset button for five 5 seconds will reboot the system and return to collect state Drain Override Drain and Test Reset buttons simultaneou...

Страница 4: ...OLLECTanDRAIN will be installed 2 Relieve air pressure from the branch line 3 Remove the existing auxiliary drain Mounting Use the four mounting tabs 3 8 holes x 4 to install the M5500 to a wall or ot...

Страница 5: ...l enclosure Refer to the electrical schematic as necessary 5 Connect the 120V AC hot wire to the top of the circuit breaker 6 Connect the 120V AC neutral wire to one of the neutral N terminals 7 Conne...

Страница 6: ...set the red thermostat set point dial to the factory default setting of 50 F NOTE It is the owner s responsibility to set the thermostat based upon the climate conditions of the installed location The...

Страница 7: ...e local drain button is pressed or if it has been wired the remote button is pressed While the alarm is active an auxiliary contact is also triggered and is capable of being wired back to a central co...

Страница 8: ...ity installation location and exposure to sunlight The following graph shows an estimation of the daily energy consumption verses the ambient temperature when the set point is 50 F The M5500 features...

Страница 9: ...n cycle the PLC senses a malfunction such as the valves not fully actuating or the condensate not draining from the system the system alarm will stay on or enter the alarm state Refer to the Quick Ref...

Страница 10: ...n condensation from the system or conduct regularly scheduled testing and maintenance could result in system failure due to freezing System must be maintained per NFPA 25 It is especially important th...

Страница 11: ...oor of the M5500 electrical enclosure 3 Turn the red Thermostat Set Point Dial clockwise or counterclockwise to the desired setting 4 Take note of the new thermostat set point Thermostat Set Point ___...

Страница 12: ...AGF Manufacturing Inc 100 Quaker Lane Malvern PA 19355 Phone 610 240 4900 Fax 610 240 4906 www agfmfg com...

Отзывы: