AGA MUCH WENLOCK CLASSIC Скачать руководство пользователя страница 4

existing masonry chimney should be sound and if
necessary inspected and repaired by a competent
mason. It may be necessary to line the chimney
using a suitable stainless steel flue liner.  The stove
must be connected to a chimney with a minimum
continuous draught of 12 Pascal’s to obtain nominal
output. Poor draught conditions will result in poor
stove performance.  Allowing for an access into the
chimney at the lower end will facilitate cleaning.
Chimneys for use with solid fuel appliances should
be capable of withstanding a temperature of 1100°C
without any structural change which would impair
the stability or performance of the chimney.

VENTILATION & COMBUSTION AIR REQUIRE-
MENTS

This appliance is rated at less than 6kW.  It is imper-
ative that there is sufficient air supply to the stove in
order to support correct combustion. The air supply
to this appliance must comply with B.S. 8303: Part 1
and current Building Regulations. The minimum
effective air requirement for this appliance is 5.5
cm

2

.  If a draught stabiliser is used then this increas-

es to 23.5 cm

2

. When calculating combustion air

requirement for this appliance use the following
equation:  a total free area of at least 550mm

2

per

kW of rated output above 5kW shall be provided.  

If same or adjacent room, it will be necessary to cal-
culate additional air supply.  All materials used in the
manufacture of air vents should be such that the
vent is dimensionally stable and corrosion resistant.

The effective free area of any vent should be ascer-
tained before installation. The effect of any screen
should be allowed for when determining the effective
free area of any vent.  

Air vents direct to the outside of the building should
be located so that any air current produced will not
pass through normally occupied areas of the room.
An air vent outside the building should not be locat-
ed less than the dimensions specified within the
Building Regulations from any part of any flue termi-
nal. These air vents must also be fire proofed as per
Building Regulations.

Air vents traversing cavity walls should include a
continuous duct across the cavity. The duct should
be installed in such a manner as not to impair the
weather resistance of the cavity.  Joints between air
vents and outside walls should be sealed to prevent
the ingress of moisture.  Existing air vents should be
of the correct size and unobstructed for the appli-
ance in use.  If there is an air extraction fan or other
air using appliance fitted in the room or adjacent
rooms where this appliance is fitted, additional air
vents will be required to alleviate the possibility of
spillage of products of combustion from the appli-
ance/flue while the fan is in operation.  Where such
an installation exists, a test for spillage should be
made with the fan or fans and other appliances

using air in operation at full rate, (i.e. extraction fans,
tumble dryers) with all external doors and windows
closed.  If spillage occurs following the above oper-
ation, an additional air vent of sufficient size to pre-
vent this occurrence should be installed.

FLUE PIPES

A flue pipe should only be used to connect an appli-
ance to a chimney and should not pass through any
roof space.  Flue pipes may be of any of the follow-
ing materials:

(a)  Cast iron as described in BS 41: 1973 (1981), or
(b) Stainless steel with a wall thickness of at 

least 1mm and as described in BS EN 
10095:1999 Specification for stainless and 
heat resisting steel plate, sheet and strip, for
Grade 316 S11, 316 S13, 316 S16, 316 
S31,316 S33, or the equivalent Euronorm 88-
71 designation, or

(c)  Vitreous enamelled steel complying with 

BS 6999: 1989.

Flue pipes with spigot and socket joints
should be fitted with the socket upper most.
Clearance to combustibles must be
adhered to when fitting the flue pipe. The
flue gas mass flow is 4.56 g/s mineral fuel
and 4.11 g/s wood logs. The mean flue gas
temperature directly downstream of the
spigot at nominal heat output is 275 °C. The
appliance is suitable for continuous opera-
tion on solid mineral fuel and intermittent
operation on wood logs.

TOP FLUE EXIT

For top outlet configuration remove the hob from the
top of the stove, turn the hob upside down and place
it on the floor, taking care not to damage it.  Remove
the hob blanking plate by unscrewing the two
screws from underneath the hob.  Next remove the
flue blanking plate from the top of the stove by
unscrewing the two screws, connect this blanking
plate to the rear flue outlet at the back of the stove.
Replace the hob in the correct position.  Connect the
connector pipe (not supplied) into the top flue outlet
socket at the top of the stove and cement into place
using approved fire cement ensuring that no cement
blocks the flue passageway.

4

Содержание MUCH WENLOCK CLASSIC

Страница 1: ...WARNING This appliance is hot while in operation and retains its heat for a long period of time after use Children aged or infirm persons should be supervised at all times and should not be allowed to...

Страница 2: ...tection 5 12 Specification 6 13 Lighting 7 14 Important Notes 8 15 Operating Instructions 9 16 Primary Air Settings 9 17 Recommended Fuels 9 18 Air Wash Settings 9 19 Tertiary Air System Control 9 20...

Страница 3: ...least 181cm2 or a diameter of at least 150mm It is best to connect to a chimney of the same size as con nection to a larger size may result in a somewhat less draught This appliance is not suitable f...

Страница 4: ...ls should be sealed to prevent the ingress of moisture Existing air vents should be of the correct size and unobstructed for the appli ance in use If there is an air extraction fan or other air using...

Страница 5: ...earances to com bustibles INSTALLATION CLEARANCES Clearance to combustible materials From the front 900mm From the sides 600mm From the back 700mm From the flue pipe 600mm The connector may pass throu...

Страница 6: ...Boiler Nominal Output Wood Logs 5 5 kW Solid Mineral Fuel 4 1 kW Typical refuelling intervals to obtain nominal outputs 1 5 hours wood 4 hours solid mineral fuel WARNING DO NOT OBSTRUCT PRIMARY AIR SU...

Страница 7: ...ell alight open the fire door and add more kindling of a larger size to sustain the fire Close the firedoor Do not operate this appliance with the firedoor open 8 Never use inflammable liquid i e gaso...

Страница 8: ...air ventilation to ensure plenty of air for combustion 8 Do not use as an incinerator burning rubbish household waste 9 Do not leave fire door open for long periods as this will over heat the unit cau...

Страница 9: ...ry to set properly and to season the stove RECOMMENDED FUELS This appliance has been tested using seasoned wood logs and manufactured briquetted smokeless fuel Ancit for closed appliances sized betwee...

Страница 10: ...oor and re set the spin valve to the required setting DE ASHING Never allow the ashpan to over fill as it will cause damage to the grate When ash build up becomes excessive in the fire chamber riddle...

Страница 11: ...condition observe the following tips 1 Wipe over daily with a soapy damp cloth followed by a polish with a clean dry duster 2 For stubborn deposits a soap impregnated pad can be carefully used on the...

Страница 12: ...1 ASHPAN 1 12 RATING PLATE BRACKET 2 13 AIR SLIDER PLATE 2 14 SIDE BRICK 1 15 BRICK FOR DRY SHELL 1 16 SPRING HANDLE 1 17 FIRE DOOR ASSEMBLY 1 18 HINGE WASHER 1 19 DATA PLAQUE 1 20 DRY SHELL PROTECTIO...

Отзывы: