AGA MUCH WENLOCK CLASSIC Скачать руководство пользователя страница 3

MUCH WENLOCK SOLID FUEL NON BOILER STOVE

INSTALLATION & OPERATING INSTRUCTIONS

GENERAL

When installing, operating and maintaining your
stove respect basic standards of fire safety. Read
these instructions carefully before commencing the
installation.  Failure to do so may result in damage
to persons and property. Consult your local
Municipal office and your insurance representative
to determine what regulations are in force. Save
these instructions for future reference.

PRE INSTALLATION ASSEMBLY

1. After removing the stove from its pack,open the 

front door and remove the contents.

2. Fit the front door handle.
3. Remove the stove from the wooden pallet.
4. Fit the front ash tray by slotting into place on the

front and secure it  using the screws provided.

3

The installation must be completed in accor-
dance with current National and European
Standards and Local Codes. It should be noted
that the requirements and these publications
may be superseded during the life of this 
manual.

Fig.1

CHIMNEY

This stove is a radiant room heater and must be con-
nected to a chimney of the proper size and type.The
chimney must have a cross-sectional area of at least
181cm

2

or a diameter of at least 150mm.  It is best

to connect to a chimney of the same size, as con-
nection to a larger size may result in a somewhat
less draught. 

This appliance is not suitable for installation in a
shared flue system.

The appliance requires minimum chimney height of
4.5 metres from floor on which stove is installed. An 

Fig 2

2300

FLUES

Flues should be vertical wherever possible and
where a bend is necessary, it should not make an
angle of more than 45

o

with the vertical.  Horizontal

flue runs should be avoided except in the case of a
back outlet from the appliance, when the length of
the horizontal section should not exceed 150mm.

In order to minimise flue resistance and to make
sweeping easier it is recommended to use 2 x 45

o

bends rather than a 90

o

bend.

The flue termination point must be located to min-
imise any wind effects.  Wind effects of suction,
pressure zones and turbulence can be created by
the roof and adjacent objects.  Wind effects can also
be created by natural land contours.

To minimise the wind effects, the flue termination
point should be located a minimum of 1000mm from
the roof measured vertically and 2300mm measured
horizontally.  Where this termination point does not
suffice it may be necessary to extend the flue pipe
so that the termination point is above the apex. 

Appliance

Soot Door

1000

Содержание MUCH WENLOCK CLASSIC

Страница 1: ...WARNING This appliance is hot while in operation and retains its heat for a long period of time after use Children aged or infirm persons should be supervised at all times and should not be allowed to...

Страница 2: ...tection 5 12 Specification 6 13 Lighting 7 14 Important Notes 8 15 Operating Instructions 9 16 Primary Air Settings 9 17 Recommended Fuels 9 18 Air Wash Settings 9 19 Tertiary Air System Control 9 20...

Страница 3: ...least 181cm2 or a diameter of at least 150mm It is best to connect to a chimney of the same size as con nection to a larger size may result in a somewhat less draught This appliance is not suitable f...

Страница 4: ...ls should be sealed to prevent the ingress of moisture Existing air vents should be of the correct size and unobstructed for the appli ance in use If there is an air extraction fan or other air using...

Страница 5: ...earances to com bustibles INSTALLATION CLEARANCES Clearance to combustible materials From the front 900mm From the sides 600mm From the back 700mm From the flue pipe 600mm The connector may pass throu...

Страница 6: ...Boiler Nominal Output Wood Logs 5 5 kW Solid Mineral Fuel 4 1 kW Typical refuelling intervals to obtain nominal outputs 1 5 hours wood 4 hours solid mineral fuel WARNING DO NOT OBSTRUCT PRIMARY AIR SU...

Страница 7: ...ell alight open the fire door and add more kindling of a larger size to sustain the fire Close the firedoor Do not operate this appliance with the firedoor open 8 Never use inflammable liquid i e gaso...

Страница 8: ...air ventilation to ensure plenty of air for combustion 8 Do not use as an incinerator burning rubbish household waste 9 Do not leave fire door open for long periods as this will over heat the unit cau...

Страница 9: ...ry to set properly and to season the stove RECOMMENDED FUELS This appliance has been tested using seasoned wood logs and manufactured briquetted smokeless fuel Ancit for closed appliances sized betwee...

Страница 10: ...oor and re set the spin valve to the required setting DE ASHING Never allow the ashpan to over fill as it will cause damage to the grate When ash build up becomes excessive in the fire chamber riddle...

Страница 11: ...condition observe the following tips 1 Wipe over daily with a soapy damp cloth followed by a polish with a clean dry duster 2 For stubborn deposits a soap impregnated pad can be carefully used on the...

Страница 12: ...1 ASHPAN 1 12 RATING PLATE BRACKET 2 13 AIR SLIDER PLATE 2 14 SIDE BRICK 1 15 BRICK FOR DRY SHELL 1 16 SPRING HANDLE 1 17 FIRE DOOR ASSEMBLY 1 18 HINGE WASHER 1 19 DATA PLAQUE 1 20 DRY SHELL PROTECTIO...

Отзывы: