It is recommended that the range be serviced at regular annual
intervals.
Arrange with the householder that the range has been turned

OFF

the night before to ensure it is cold upon arrival.

The appliance and its individual shut-off valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressure in excess of 1/2
psig (3.5kPa). The appliance must be isolated from the gas
supply piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply piping
system at test pressure equal to or less than 1/2 psig (3.5kPa).

1. Isolate the gas supply by turning off the service gas valve 

beneath the combination gas valve. Break the hexagon 
union connection nut.

2. Detach inner burner door fixing screws and draw 

complete gas burner assembly clear of the combustion 
chamber resting it on the floor in front of the range.

NOTE:

THERE IS SUFFICIENT LENGTH OF 

THERMOSTAT CAPILLARY TUBE WITHOUT DETACHING
THE SENSING END FROM THE TOP OF THE ROASTING
OVEN.

3. Remove the boiling plate, combustion chamber baffle 

and simmering plate.

4. Check conditions of flueways and combustion 

chamber and clean if necessary.

5. Lightly brush the perforated top of the gas burner and 

check that the burner venturi is free of lint and fluff.

NOTE:

IT MAY BE NECESSARY TO DETACH THE PILOT

ASSEMBLY AND REMOVE THE BURNER TO ENSURE IT
IS FREE.

6. Check the condition of the pilot thermocouple tip to ensure 

it is clean and free of carbon. Heavy heat oxidised tips 
should mean the removal of the thermocouple and a new 
replacement. Examine and brush clean the pilot light parts 
and examine the ignitor cable and connector strip to ensure  
the PTFE insulation cable, remains intact and strip is
firmly connected to the spark electrode. Clean any carbon 
away from the electrode.

7. Refit combustion chamber baffle.

8.

DIRECT VENT MODEL ONLY - GC AND GE.

Using a wire brush, lightly remove the old sealing cement 
on the contact under faces of the hotplate and simmering 
plates to the cooker, and lighly smear another cement 
sealing coat provided, before refitting of hotplates.

9. Refit gas burner assembly in reverse manner described in 

2 and reconnect the gas supply at service gas valve union.
On completion test the gas installation for soundness and 
purge. Leak testing of the appliance shall be conducted 
according to manufacturer’s instructions.
NOTE: USE SOAPY WATER SOLUTION ON NEW GAS 

CONNECTIONS TO ENSURE THERE ARE NO GAS 
LEAKS.

10. Turn on the gas supply and follow the procedure for 

lighting the burner.

11. Ensure that the pilot and main burner flames are 

burning evenly, the thermocouple is enveloped by the 
pilot flame.

12. Visually check main burner and pilot flame for correct 

flame pattern. An established main burner at high fire will 
be predominantly blue with yellow tippings on an even 
height flame strip and be about 150mm (6in) high. See Fig.
11. Ensure all flameports have cross-lit and that the pilot 
light flame is free from sooting.

13. The maximum depth of any cabinets installed above the 

top cooking surface of the range must not exceed 330mm 

(13in).

8

With Aga's policy of continuous product improvement, the

Company reserves the right to change specifications and make

modifications to the appliance described and illustrated at any time.

Aga-Ranges
110 Woodcrest Road
Cherry Hill
NJ 08003
800.633.9200

Installer Servicing Instructions for Aga Models
GC and GE Open Flue Ranges and
GC and GE Direct Vent Ranges

YEARLY SERVICE

www.aga-ranges.com

For further advice or information please contact
your local distributor/stockist 

Содержание GC Open Flue Range

Страница 1: ...rial for a minimum thickness of 12mm 1 2in and comply with current Building Regulations and National Fire Laws The wall behind the cooker draft hood and flue connector must have a minimum air gap of 5...

Страница 2: ...ng types of vent i Type B Vent 25mm 1in minimum ii Single wall vent connector 150mm 6in minimum Listed connectors passing through combustible walls and partitions must be guarded by a ventilated metal...

Страница 3: ...ly from the bottom of an openable window air vent or any other ventilating opening b Within 300mm 12in above adjacent ground level c Within 600mm 24in of any surface facing the terminal d Within 355mm...

Страница 4: ...ly piping system at test pressures equal to or less than 1 2 psig 3 5kPa The model and serial numbers for this appliance are found on the name plate These numbers must be used when requesting advice f...

Страница 5: ...tablished release the control knob gradually and rotate anti clockwise to its low fire position whereupon the main burner will light Leave in the low fire position for at least 30 minutes NOTE Any att...

Страница 6: ...ows Description 1 Pilot Thermocouple 2 Main Burner 3a Pilot Burner Assembly N G 3b Pilot Burner Assembly L P G 4 Combination Gas Valve 5a Pressure Regulator N G 5b Pressure Regulator L P G 6 Combustio...

Страница 7: ...7 Fig 12 Pilot Thermocouple DESN 512827...

Страница 8: ...he PTFE insulation cable remains intact and strip is firmly connected to the spark electrode Clean any carbon away from the electrode 7 Refit combustion chamber baffle 8 DIRECT VENT MODEL ONLY GC AND...

Отзывы: