Page 22
CT
Control Type
FI
Metered (Flow) Immediate - will regenerate imme-
diately after programmed capacity is reached.
Fd
Metered (Flow) Delayed - will regenerate at the
preset time after programmed capacity is reached.
Tc
Time Clock - will regenerate at the set regeneration
time after the set number of days has passed.
dAY
Day of the Week - will begin a regeneration cycle
on the set day(s) at the set regeneration time.
NT
Number of
Tanks
1
For systems with only 1 media tank.
2
For systems with 2 media tanks (dual tank soften-
ers only).
UT
Indicates
current tank
in service
U1
Tank 1 is in service
U2
Tank 2 is in service (dual tank softeners only).
C
Capacity
1-999.9
(x1000)
System capacity, in grains
H
Hardness
1-199
Hardness of the water, in grains.
RS
Reserve
Selection
SF
Percentage safety factor - a percentage of total
capacity
rc
Fixed reserve capacity - a set number of gallons
SF
Safety Factor
0-50%
Sets safety factor if RS is set to SF
RC
Reserve
Capacity
1-(half of
calculated
capacity)
Sets the number of gallons to use as a reserve on
systems with RS set to rc
DO
Day Override
OFF-99
Initiates the regeneration at the set number of
days, regardless of usage.
RT
Regen Time
12:00
This sets the time that the regeneration cycle will
start.
BW
Backwash
0-199
This sets the length of the backwash portion of the
cycle.
BD
Brine Draw
0-199
This sets the length of the brine draw portion of
the cycle.
RR
Rapid Rinse
0-199
This sets the length of the rapid rinse cycle.
BF
Brine Fill
0-199
This sets the length of the brine fill portion of the
cycle.