12
Mounting
EN
HMS
5
Mounting
5.1
Mounting the photoelectric probe
The probe is factory-connected to the control unit.
Verify that the probe is submerged even in the case of small amounts of
liquid.
Verify that the tip of the probe is not subjected to mechanical load.
1. Mount the photoelectric probe at the lowest point of the area to be moni-
tored (lying or suspended).
- The probe must not hang directly on the control unit.
2. Use the holder supplied with the product or a cable clamp to provide strain
relief for fastening.
3. Place the probe at a position where there is little or no influencing light.
5.2
Mounting the bracket
NOTICE
UNAVAILABLE MEASURING FUNCTION
•
The probe is not intended to be permanently submerged in liquid.
NFailure to follow these instructions can result in equipment damage.
1. Mount the bracket to a wall or a
container (vertical or horizontal)
using a screw.