Mounting and commissioning
– English –
DIT 10
36
Fig. 6: Inserting the pressure sensor into the tank
5.
At the cable gland, adjust the cable length of the sensor cable in
such a way that the probe tip reaches the tank bottom. The
measuring hole of the pressure sensor must not be immersed in
sludge that may be present at the tank bottom. Any volume of
liquid below the measuring hole of the pressure sensor is not
detected by the pressure sensor.
6.
Only fit the withdrawal hose after you have inserted the pres-
sure sensor.
Fig. 7: Fitting the withdrawal hose
7.
Seal the cable gland into tank cover so that it is odour-tight and
secure the cable so that it cannot move.