Page

Figure 5

Technical specifications

Warranty

Customer satisfaction

Taking out of service, disposal

Approvals and certificates

Setting the auxiliary switch (selected versions)

Maintenance

Operation of the actuator

Procedure for setting the auxiliary switch:

1. 

3. 

5. 

4. 

2. 

Loosen two fixing screws "i" and 

remove the actuator housing 

(fig. 1)

.

Carefully push in the ring in such a way that

the end of the thicker section of the 

circumference coincides with the specified 

switch triggering angle.

Refit the upper part of the actuator housing

and tighten the fixing screws "i".

After the actuator has been set to position

"5" of the adjustment scale at the adjustment

handle (50 % open) and the valve opening 

direction has been determined, set the angle

of the actuator (range 0 - 90°) at which the

function of the auxiliary switch is to be 

triggered.

Carefully remove the switching ring 

(fig. 5)

. The thicker ring section which

moves below the switch while the 

actuator operates, applies pressure to

the lever and thus opens  of contacts 

4-5 of the auxiliary switch.The function 

of the auxiliary switch (closing of 

contacts 4-5) is initiated when the 

thinner ring section faces the switch 

which triggers the lever. At the same 

time, the signal lamp lights up.

The AFRISO ARM actuator is maintenance-free.

 

 

 

 

 

 

 

3-point

2-point

proportional

3-point + auxiliary switch

3-point + auxiliary switch

The electrical actuator ARM complies with the Low Voltage Directive (LVD) (2006/95/EC),

Electromagnetic Compatibility Directive (EMC) (2004/108/EC) and Restriction 

of Hazardous Substances Directive (RoHS) (2002/95/EC)
The electrical actuator ARM also complies with the following standards: 

EN 60730-1, EN60730-2-14.

 

 

 

 

 

 

 

 

The warranty of the manufacturer for this 

product is 36 months after the date of 

purchase. The warranty shall be void if 

unauthorised modifications are made to the 

product or if the product is not installed in 

compliance with these instructions.

Customer satisfaction is the prime objective of 

AFRISO-EURO-INDEX. Please contact us at 

[email protected] if you have any questions, 

suggestions or problems concerning product.

 

 

 

 

1. 

2. Dismount the device. 
3. To protect the environment, this 

    device must not be disposed of 

    together with non-separated 

Disconnect the device from the 

supply voltage.

 

 

commercial waste. Take the device to

an official waste disposal company. 

The electrical actuator ARM consists of 

recyclable materials.

 

 

 

1. Operating mode of the actuator 

 

 

 

2. Indication via signal LEDs

The operating mode is set by means of 

the selector for manual mode "j" 

(fig. 1)

Operating mode Automatic:

 The actuator 

is in operating mode Automatic when the 

selector "j" is in position     .

Operating mode Manual:

 The actuator is in

 operating mode Manual when the selector 

"j" is in position    .

 

Three signal LEDs are integrated into the 

housing of the actuator. The outer LEDs 

indicate the direction of rotation of the

actuator. The centre LED indicates the 

operating state of the auxiliary switch 

(depending on the version of the actuator).

 

   

 

 

 

 

 

 

 

3. Position of adjustment handle with 

adjustment scale

After the actuator has been mounted to the

mixing valve and the proper adjustment 

scale selected, position "0" means that the 

valve is fully closed (hot water supply 

closed) and position "10" means that the 

valve is fully opened (hot water supply 

open). The other settings of the adjustment

scale represent the degree of opening 

(for example, "4" means that the valve is

open by 40%).

orange

 

(direction of rotation left)

 

 

orange

(direction of rotation right)

 

 

red

(auxiliary switch active)

 

 

 

Parameter

Value

Torque

Depending on version:

 

   

 6 Nm, 10 Nm, 15 Nm

Rotation angle

 

90°

Time for turn by

 

    90°

Depending on version:

 

   

  

15 s, 30 s, 60 s, 120 s, 240 s, 480 s

Supply voltage / control signal

2-point  

- 24 V AC / 230 V AC

3-point  

- 24 V AC / 230 V AC

proportional - 24 V AC/DC

(0..10 V, 2..10 V, 0..20 mA, 4..20 mA)

Operating temperature range

 

Setting in range

   

 0 ÷ 90° (250 V AC, 3 A)

Power input

 

 

0 ÷ 50°C

Power consumption

 

2,5 ÷ 4 VA

Protection class

 

II

Degree of protection

 

 

IP42

Dimensions (H x W x D):

84 × 102 × 90 mm

Weight

Version  6 Nm: 390 g ÷ 630 g 

Version 10 Nm and  15 Nm: 600 g ÷ 860 g

Housing material

 

PC

instrukcja prosta do pudelka.indd   2