Electrical

 

Connection

 

Notes:

 

1.

 

After

 

the

 

inverter

 

has

 

been

 

installed

 

in

 

its

 

fixed

 

position,

 

the

 

electrical

 

connection

 

to

 

the

 

unit

 

can

 

be

 

established.

 

2.

 

Make

 

sure

 

Max.

 

Open

 

Voltage

 

and

 

short

circuit

 

current

 

of

 

the

 

PV

 

string

 

accord

 

with

 

the

 

Spec.

 

3.

 

Choose

 

the

 

appropriate

 

cable

 

width

 

for

 

AC/DC

 

wire.

 

4.

 

To

 

connect

 

the

 

inverter,

 

the

 

AC

 

and

 

DC

 

side

 

must

 

be

 

disconnected

 

from

 

all

 

power

 

sources

 

and

 

secured

 

against

 

being

 

inadvertently

 

switched

 

back

 

on.

 

5.

 

Before

 

connecting

 

inverter

 

to

 

PV

 

modules

 

and

 

public

 

grid,

 

please

 

make

 

sure

 

the

 

polarity

 

is

 

correct.

 

Electrical

 

connections

 

should

 

comply

 

with

 

the

 

National

 

Wiring

 

Rules

 

of

 

Standard

 

AS/NZS

 

3000.

 

The

 

requirements

 

in

 

AS

 

4777.1

 

and

 

AS/NZS

 

3000

 

indicate

 

that

 

a

 

DC

 

isolator

 

must

 

be

 

used

 

before

 

the

 

inverter.

 

5.1

 

Overview

 

of

 

the

 

Connection

 

Area

 

The

 

following

 

figure

 

shows

 

the

 

assignment

 

of

 

the

 

individual

 

connection

 

areas

 

on

 

the

 

bottom

 

of

 

the

 

inverter.

 

 

 

 

Содержание HNS1509TL

Страница 1: ...USER MANU HNS150 UAL IN 00TL HNS NSTALLA S2000TL ATION ...

Страница 2: ...ssembly parts 2 3 2 Identifying the Inverter 3 4 Mounting the Device 3 4 1 Selecting the appropriate Mounting Location 4 4 2 Mounting the Inverter with the Wall Mounting Bracket 5 5 Electrical Connection 6 5 1 Overview of the Connection Area 6 5 2 Connection to the Public Grid AC 7 5 3 Connection of the PV Generator DC 9 5 4 Communication 11 6 Commissioning 11 7 System Diagram 11 8 Specification 1...

Страница 3: ...s 2 1 safety precautions 1 All work on the inverter must be carried out by skilled electricians 2 The device may only be operated with PV generators Do not connect any other source of energy to the device 3 The PV generator and inverter must be connected to the ground in order to reach maximum protection for property and persons 4 Before opening the cabinet the inverter must be disconnected from t...

Страница 4: ...lectricity generators and public grid Do not dispose of this device with the normal domestic waste Without Transformer This inverter does not use transformer for the isolation function CE mark The inverter complies with the requirements of the applicable EC guidelines C Tick mark The inverter complies with the requirements of Australian Communications Authority guidelines Notes Important Non adher...

Страница 5: ... Serial No and type of the inverter as well as device specific characteristics are specified on the type label The type label is on the right side of the enclosure 4 Mounting the Device DANGER Danger to life due to potential fire or electricity shock Do not install the inverter near any inflammable or explosive items The inverter will be directly connected with high voltage power generation device...

Страница 6: ...ke noises when in use Vertical installation or tilted backward by max 30 degree is allowed Never mount the device with a forward tilt horizontally or even upside down For the convenience of checking the LCD display and possible maintenance activities please install the inverter at eye level The ambient temperature of installation site should be between 20 C and 40 C between 4 F and 104 F Install t...

Страница 7: ...the wall mounting bracket to the wall using appropriate screws diameter min 6 mm max 8 mm and washers outer diameter min 12 mm max 24 mm 3 Hang the inverter to the mounting bracket and check the upper slot is fitted on the bracket 4 Check to ensure the inverter is correctly seated and insert the safety lock screws to the both sides to secure the inverter ...

Страница 8: ...must be disconnected from all power sources and secured against being inadvertently switched back on 5 Before connecting inverter to PV modules and public grid please make sure the polarity is correct Electrical connections should comply with the National Wiring Rules of Standard AS NZS 3000 The requirements in AS 4777 1 and AS NZS 3000 indicate that a DC isolator must be used before the inverter ...

Страница 9: ...or each inverter in order that the inverter can be safely disconnected under load 5 2 2 Connecting to the Public Grid AC Overview of the AC Coupling Socket Object Description A Socket for the AC connection plug B Socket element C Threaded sleeve with sealing ring for cable diameters from 10 mm to 14 mm D Sealing ring for cable diameters of 6 mm to 10 mm E Clamping nut Connecting to the Public Grid...

Страница 10: ...the grounding conductor PE green yellow in the screw terminal with the earth sign on the socket screw the neutral conductor N blue in the screw terminal N on the socket element and phase L brown or black into the screw terminal L on the socket element then tighten the screw to make sure the wires are securely connected After fasten the three wires with the terminal combine every component together...

Страница 11: ... inverter can be safely installed 5 3 1 Conditions for the DC Connection The connected PV modules must meet following requirements Same type Same number Identical alignment Identical tilt The following limit values at the DC input of the inverter must not be exceeded connecting to a higher voltage will destroy the device Anyhome Maximum input voltage Maximum input current 1 5KW 500V 8A 2KW 500V 12...

Страница 12: ...ure all conductor strands are captured in the contact barrel Please see below figures 3 Compress them together with the crimping pliers Please see below figures 4 Insert contact cable assembly into back of male and female connector A click should be heard or felt when the contact cable assembly is seated correctly Then turn the cap to the coupler Please see below figures 5 3 3 Connecting the PV Ge...

Страница 13: ...ters can communicate and be monitored through one communication module RS485 communication module and receiver can be purchased from Afore New Energy as options And you can download the monitor software from www aforenergy com 6 Commissioning After completing the mechanical and electrical installation the inverter is put into operation 1 Switch on the DC and AC breakers The inverter starts up auto...

Страница 14: ...power from your PV panel s 3 Connection system This interface between Utility and PV Inverter may consist of electrical breaker fuse and connecting terminals To comply with local safety standards and codes the connection system should be designed and implemented by a qualified technician 4 Utility Referred to as grid in this manual is the way your electric power company provides power to your plac...

Страница 15: ...utput Current THD 4 4 Night Consumption 1W 1W Topology Transformerless Transformerless Cooling Air Cooling Air Cooling Power Efficiency Maximum Efficiency 96 50 96 50 European Efficiency 95 50 95 50 Packaging Dismension H X W X D 484X340X145 484X340X145 Enclosure IP65 IP65 Operating Temp Range 20 40 20 40 Weight kg 16 16 9 Contact If you have any technical problems concerning our products you can ...

Отзывы: