33
IntProtectP
Frequency fault protection
Reset grid frequency in accordance to local grid standard
IntProtectQ
DCI too high protection
Please contact with local dealer if error remains the same after
several reset.
IntProtectR
DCI offset protection
Please contact with local dealer if error remains the same after
several reset.
IntProtectS
Voltage offset protection
Please contact with local dealer if error remains the same after
several reset.
IntProtectT
PV over current protection
Please contact with local dealer if error remains the same after
several reset.
IntProtectU
Internal
hardware
abnormal
protection
Please contact with local dealer if error remains the same after
several reset.
IsolationErr
1.PV(+) or PV(-) earthing
2.Lightening
3.Machine failure
1.Check
PV(+)
and
PV(-)
ground impedance
,
make
sure impedance is more than 2M
Ω
.
2.Please contact with after-sales if error remains the same
after several reset.
PV.Reverse
1.PV polarity reverse protection
2.Machine failure
1.Turn off input/output switch,
check if pv polarity is correct or
not, for troubleshooting.
2.Please contact with after-sales if error remains the same
after several reset.
PVVoltOver
PVThe input voltage is too high
1. Adjust the panel configuration to lower the input voltage.
2.Please contact with local dealer if error remains the same
after several reset.
SPICommErr
SPI communication error
Please contact with local dealer if error remains the same after
several reset.
TempOver
1.The machine is exposed to sun.
2.the ambient temperature is too
high
3.The heatsink
or fan blocked by foreign matter
4.Machine failure
1. Lower machine surrounding temperature or move it to a
lower temperature place.
2. Remove foreign matter.
3.Please contact with local dealer if error remains the same
after several reset.
TempSensorErr Abnormal temperature sensor
Please contact with local dealer if error remains the same after
several reset.
ExtFanErr
1.Fan blocked by foreign matter
2.Machine failure
1.Remove foreign matter.
2.Please contact with local dealer if error remains the same
after several reset.
IntFanErr
Internal fan fault
Please contact with after-sales if error remains the same after
several reset.
Restart: Disconnect input and output switches in order, reconnect them after LCD and indicating lights go off.
If there is no display on the LCD, please check both AC and DC wiring.
If the input DC voltage is higher than start up voltage, the inverter still doesn’t work, please call local service.
If it is intended to replace the cable or open the enclosure lid, please call our service.
Under the low light conditions, the inverter may continuously start up and shut down. It is due to insufficient
power generated to operate the control circuits.