SK2014-SON-002-TechMnl-SWC-003
a)
MTV2, AUX1 and heater are always off.
b)
If Tr ≥ 25ºC, then MTV1 and AUX2 will be turned on for 3 minutes, and then off for 4 minutes.
c)
If 16ºC ≤ Tr < 25ºC, then MTV1 and AUX2 will be turned on for 3 minutes, and then off for 6 minutes.
d)
If Tr <16ºC, then MTV1 and AUX2 will be turned off for 4 minutes.
At the end of the above dehumidification cycle, the system will decide the next dehumidification control option.
Indoor fan will run at low speed throughout the dehumidification process.
AUTO-MODE
a)
If the current running mode is AUTO COOL mode, it will change over to AUTO HEAT mode upon satisfying all
the conditions below:
1)
Ts – Tr ≥ 1°C (or – 4ºC if economy contact is activated).
2)
MTV1 has stopped ≥ 10 minutes.
b)
If the current running mode is AUTO HEAT mode, it will change over to AUTO COOL mode upon satisfying all
the conditions below:
1)
Tr - Ts ≥ 1°C (or + 4ºC if economy contact is activated).
2)
MTV2 has stopped ≥ 10 minutes.
Note: AUTO COOL or AUTO HEAT operations are the same as COOL or HEAT mode respectively.
SLEEP MODE
a)
SLEEP mode can only be set when the unit is in COOL or HEAT mode.
b)
In COOL mode, after SLEEP mode is set, the indoor fan will run at low speed and Ts will increase by 2ºC over 2
hours.
c)
In HEAT mode, after SLEEP mode is set, the indoor fan will run at set speed and Ts will decrease by
2ºC over 2 hours.
d)
Changing of operation mode will cancel SLEEP mode.
C.1.7.
Auto Fan Speed
a)
In COOL mode, the fan speed cannot change until it has run for more than 30 seconds.
b)
In HEAT mode, the fan speed cannot change until it has run for more than 30 seconds.
C.1.8.
Louver
For remote handset
Whenever the indoor fan is running, the louver can swing or stop at the desired position.
Louver angle: 0~100º, opens clockwise with widest angle at 100º.
Swing angle: 35~100º, opens clockwise to 68º. Below are the 4 fixed positions which can be set from wireless
LCD handset.
Position
Angle
1
35º
2
57º
3
83º
4
100º
For wired wall pad
Louver angle: 0~100º, opens clockwise with angle at 100º.
Swing angle: 35~100º, opens clockwise to 68º. User may stop louver at any desired position between 35~100º.
C.1.9.
Buzzer
If a command is received by the air conditioner, the master unit will respond with 2 beeps for each setting,
while the slave unit will respond with 1 beep.
C.1.10.
Auto Restart