background image

Aerox

®

 Aviation Oxygen Systems, LLC 

12871 Trade Way Drive, Suite 8 

Bonita Springs, FL  34135 

www.aerox.com

 

[email protected]

 

 

Page 11 

 

Cylinder 

Type 

Hydrostatic Test & 

Inspection Rqmt 

Maximum 

Service Life 

 

DOT 3AL 

 

Every 5 Years 

 

Unlimited 

6061T6 Alum 

49 CFR § 180.209  

 

DOT 3HT 

Every 3 Years 

24 Years 

Steel 

49 CFR § 180.209 

 

DOT-E 8162 

Every 5 Years 

15 Years 

Kevlar/Comp 

49 CFR § 180.209 

(10,000 Cycles) 

DOT-E 10945 

Every 5 Years 

15 Years 

Carbon/Comp 

49 CFR § 180.209 

(10,000 Cycles) 

 

Cylinder Purge 

Cylinder pressures below 50 PSI may allow air into the cylinder. Air contains 
moisture and under certain temperature extremes can freeze and plug oxygen 
ports and lines. 

 

The most effective method to purge the cylinder of any suspected moisture is to 
remove the regulator/valve and with the cylinder turned so the threads are 
down, blow hot air (heat gun or hair dryer) into the cylinder for about 20 minutes 
or until all moisture has evaporated. 

Where a cylinder has been exposed to an extended period of low storage 
pressure, a cleaning and inspection by a licensed maintenance facility is 
recommended. 

Re-Filling 

Verify the condition and cleanliness of all ports and fittings prior to performing 
re-filling operations. 

When re-installing the regulator or valve, assure that the proper approved o-
ring or seal has been installed. 

Charge the oxygen cylinder as discussed in 

Initial Filling

Upon completion of filling operations, check for leakage using a liquid leak 
detector or a mild soapy water formula. 

 

Содержание Sky-Ox

Страница 1: ...Aerox Aviation Oxygen Systems LLC 12871 Trade Way Drive Suite 8 Bonita Springs FL 34135 www aerox com info skyox com Page 1 Your Sky Ox Portable Oxygen System Use Care Guide ...

Страница 2: ...ing your needs with equally high customer service Table of Contents Page Subject Content 3 System Components 4 Operating Instructions 7 Refilling the Aluminum Cylinder 8 Refilling the Steel Cylinder 9 After Using the System 10 Oxygen Cylinder Maintenance 13 Care of Your Portable Oxygen System 13 Care of Your Oxygen Cannula 14 Table 1 Capacity Table 14 Table 2 Volume Content Table REGISTER YOUR SYS...

Страница 3: ...in well ventilated area Cylinder contains high pressure up to 2 000 pounds per square inch psi oxygen Do not drop and protect the unit from shock or damage Keep away from anyone who may not be familiar with the hazards of its improper use or handling Maintain equipment using an Aerox Approved FAA Authorized Aviation Oxygen Repair Station Follow their recommendations on proper use 7 Flow Adjustment...

Страница 4: ...pty If empty the cylinder must be filled with aviator grade oxygen before using Ready to Use Filled Cylinders are ready to use 1 Turn the On Off Valve 3 counterclockwise until fully on Turn clockwise to shut it off 2 Check the cylinder s content level on the cylinder Pressure gauge 2 This gauge will indicate how much oxygen remains in the cylinder If the indicator needle is in the red area the cyl...

Страница 5: ...hen multiple ports are being used The regulator automatically compensates when additional 1 2 or 3 breathing units are attached A setting of 0 5 liters per minute will deliver 0 5 liters of oxygen from each port The following table is found on the Regulator Liters per minute when using Oxysaver Cannula Mask 3 LPM up to 10 000 FT 1 0 LPM up to 10 000 FT 4 LPM 12 000 FT 1 5 LPM 15 000 FT 5 LPM 15 00...

Страница 6: ...m the cylinder to the cannula Sky Ox Flow Indicator showing no oxygen flow 7 A cannula either apendentoramustache style can be used onlyupto18 000ft Above18 000ft youmustswitchoverto a mask 8 When using themask set the flowadjustment control to the altitude you are flying See table on Regulator also printed on page5 ByturningtheFlowAdjustment Control 7 knobon top of the Regulator until the indicat...

Страница 7: ...letely close the On Off Valve 3 before attempting to disconnect the regulator Do Not Remove the On Off Valve 3 Remove the Regulator 5 from the valve by loosening the green Hand Tightening Grip 4 see figure below between the On Off Valve and the Regulator Turn Grip Counterclockwise The valve is a standard fitting for oxygen CGA 540 and no tools are required Aerox recommends using only aviator grade...

Страница 8: ...d steel cylinders every five years The oxygen supplier will label each cylinder when it is hydrostatically tested After cylinder is refilled make sure the regulator assembly is reattached to the cylinder valve and tighten securely with Hand Tightening Grip 4 No wrench is needed Refilling the Steel Cylinder Use the same procedures for refilling steel cylinders as for aluminum cylinders See above il...

Страница 9: ...urn the Flow Adjustment Control 7 to zero 0 2 Turn the On Off Valve 3 off by turning the knob clockwise 3 If you have removed all of the quick disconnect units reinsert one to bleed off the oxygen still in the line The flow indicator turns to red when no more oxygen is flowing 4 When the system will be inactive for more than 24 hours it is recommended that the system be shut down as described abov...

Страница 10: ...ake no less than 3 minutes to accomplish with a 2 minute rest between each stage Stage PSI 1 500 2 1000 3 1500 4 1800 5 2000 6 2250 TABLE 1 CAUTION Keep Hands and Filling Equipment Clean And Free From Oil Keep Away From Flame Or Sources Of Ignition Failure To Comply With All Cautions Could Result In Injury And Death Routine Maintenance It is important to maintain positive pressure in oxygen cylind...

Страница 11: ... lines The most effective method to purge the cylinder of any suspected moisture is to remove the regulator valve and with the cylinder turned so the threads are down blow hot air heat gun or hair dryer into the cylinder for about 20 minutes or until all moisture has evaporated Where a cylinder has been exposed to an extended period of low storage pressure a cleaning and inspection by a licensed m...

Страница 12: ...eneral Fill only with Gaseous Aviators Breathing Oxygen per MIL PRF 27210 Note that certain state federal and international regulations may apply to the handling and maintenance of oxygen cylinders based on installation and application Further information regarding oxygen cylinder maintenance and use is available upon request ...

Страница 13: ...eat and secure tightly The portable oxygen system will operate properly in either an upright or a horizontal position Always secure and restrain your system as a precaution should in flight turbulence be experienced Reminder The system is under 2000 PSI of pressure when full As a safety measure the regulator is equipped with a pressure relief valve that s designed to activate under a reduced press...

Страница 14: ... x 3 1 4 6 Lbs SK 12 9 8 07 hrs 9 CU FT AL 2 45 hrs 18 0 x 4 3 8 7 Lbs SK 12 15 13 48 hrs 15 CU FT AL 4 36 hrs 24 0 x 4 3 8 11 Lbs SK 12 24 22 42 hrs 24 CU FT AL 7 34 hrs 32 1 2 x 4 3 8 14 Lbs SK 11 20 17 33 hrs 20 CU FT Steel 5 51 hrs 17 0 x 5 1 4 15 Lbs SK 11 40 39 27 hrs 40 CU FT Steel 13 09 hrs 21 0 x 7 28 Lbs SK 11 50 46 21 hrs 50 CU FT Steel 15 27 hrs 26 0 x 7 36 Lbs Volume Content Table Tab...

Страница 15: ...a Springs FL 34135 www aerox com info skyox com Page 15 For more information on Sky Ox Products visit us at www aerox com sky ox Oxysaver Aerox Sky Ox and Click a Breath are registered trademarks of Aerox Aviation Oxygen Systems LLC Aerox Aviation Oxygen Systems LLC 2022 ...

Отзывы: