Installation, Operation & Maintenance Manual
IM-166
16
Impeller Placement
Note:
Use "B" dimension for positioning impeller.
AMX Impeller Overlap
Size
90
122
135
150
165
182
200
222
245
270
300
330
365
402
445
490
542
600
660
730
A
12.25 15.00 16.50 18.25 20.00 22.25 24.50 27.00 30.00 33.00 36.50 40.25 44.50 49.00 54.25 60.00 66.00 73.00 80.75 89.00
B
0.31 0.38 0.44 0.56 0.63 0.69 0.75 0.88 0.97 1.06 0.94 1.03 1.13 1.25 1.38 1.56 1.69 1.88 2.09 2.28
C
4.20 5.13 5.64 6.19 6.75 7.56 8.31 9.13 10.19 11.19 12.38 13.63 15.13 16.63 18.38 20.25 22.31 24.63 27.25 30.00
Model AMX