1-800-486-4328
1-204-633-1999
100 Eagle Drive
Winnipeg, MB Canada
sales@hermannelson.com
www.hermannelson.com
BURNER (OIL OPERATION)
The electrode spacing must be checked and adjusted, if necessary after every nozzle change. Nozzle should be
replaced annually or sooner if burner cannot be set up to operate properly. Nozzle size and type are marked on the
rating plate.
Distance between electrode tips must be 5/32”
Electrode tips must be ¼” from nozzle centre
Electrode tips must be 1/8” higher than nozzle tip
Nozzle and nozzle line assembly
Failure to properly set and maintain the electrode and nozzle spacing dimensions can cause incorrect burner ignition or
poor combustion. This could result in severe personal injury, death or substantial property damage.
AFTER INSPECTION, A COMPLETE COMBUSTION TEST MUST BE PEFORMED AFTER EACH ANNUAL
SERVICE OF THE UNIT TO MAINTAIN OPTIMUM PERFORMANCE AND RELIABILITY.
WARNING: TURN OFF THE FUEL SUPPLIES AND POWER BEFORE PERFORMING SERVICE
WORK. THE 120V CIRCUIT IS A POTENTIAL ELECTROCUTION HAZARD.
COMBUSTION AIR ADJUSTMENTS
BLAZE 600 D
SPECIFICATIONS
BLAZE 600D-
BECKETT (OIL)
Nozzle
2.75 GPH X 60 B
Pump Pressure
175 PSI
Head Setting
1
Air Setting (Beckett-
Shutter/Band)
3/0
NOTE:
The above settings are approximations based upon clean equipment in proper working order. Combustion air
adjustments will vary with location, altitude and type of fuel used.
WARNING: LACK OF COMBUSTION AIR CAN CAUSE A DIRTY FIRE, ODOURS IN ENCLOSED
SPACES, AND BACKDRAFTING, POTENTIALLY RESULTING IN NAUSEA OR ASPHYXIATION OF
THE OCCUPANTS.
CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768 |
www.campoequipment.com
P a g e
|
14