QM 1336.rev.01
TECHNICAL SPECIFICATIONS
Supply: - 115/230 VAC (-18%, +8%), 60 Hz, L1 same phases as Stages
1 and 2, overload and overvoltage protection fuse F11-1A fast blow.
- 12 VDC for AC back-up supply; can activate stages 3 and 4 if
supplied with DC back-up voltage.
Stage 1: Variable output, 60 Hz, 10A FAN (3/4 HP/115 VAC) / (1.5 HP/
230VAC), fuse F1-15A slow blow.
Stage 2: Variable output, 60 Hz, 10A FAN (3/4 HP/115 VAC) / (1.5 HP/
230VAC), fuse F8-15A slow blow.
Stage 3: ON-OFF output, 115/230 VAC, 60 Hz, 30VDC, 6A FAN,10A RES,
fuse F3-15A slow blow.
Stage 4: ON-OFF output, 115/230 VAC, 60 Hz, 30VDC, 6A FAN,10A RES,
fuse F4-15A slow blow.
Alarm: ON-OFF output, 115/230 VAC, 60 Hz, 30VDC, 3A, fuse F7-3A slow
blow.
Probes: Low voltage ( < 5V), isolated from the supply. Operating range:
-40.0° to 120.0°F (-40.0° to 48.9°C). Accuracy: 1.8
o
F (1
o
C) between 41
o
and
95
o
F (5
o
and 35
o
C).
Enclosure: ABS, moisture and dust-tight.
The room temperature where the controller is located MUST
ALWAYS REMAIN BETWEEN 32
o
AND 104
o
F (0
o
AND 40
o
C).