Adjusting the Mist Starting Temperature and Timer
The mist starting temperature is bounded below by the starting temperature
of the preceding cooling stage + 0.5
o
F (0.3
o
C) and above by the starting
temperature of the preceding cooling stage + 20.0
o
F (11.1
o
C). The time on
and time off parameters can take values from 0 to 60 minutes.
If Stage 3 is the mist stage:
n
Set the selection knob to
STAGE 3 — START TEMP.
The stage 3 starting tempera-
ture is displayed, alternating
with the letters "ST3".
n
Use the adjustment knob to set the starting temperature to the desired
value.
n
Press the push-button. The mist time on is displayed, alternating with
the word "On".
n
Use the adjustment knob to set time on to the desired value.
n
Press the push-button. The mist time off is displayed, alternating with
the word "OFF".
n
Use the adjustment knob to set time off to the desired value.