18

18.03. 5719210_03

ANL / 290-650

EN

8. 

ELECTRICAL CONNECTIONS

All electrical works must be carried out by PERSONNEL WITH THE APPROPRIATE LEGAL QUALI-

FICATIONS, trained and aware of the risks relating to such works.

The design of the cabling and related components must be carried out by PERSONNEL WITH 

APPROPRIATE  QUALIFICATIONS  TO  DESIGN  ELECTRICAL  INSTALLATIONS,  following  interna-

tional and national standards of the location the unit is installed, in accordance with current 

legal requirements.

For installation details refer to the electrical wiring schematics supplied with the unit. The 

electrical  wiring  schematic  together  with  the  manuals  must  be  conserved  with  care  and 

MADE AVAILABLE FOR FUTURE REFERENCE

.

T

he weatherproof seals of the equipment must be checked before making electrical connec-

tions and the unit most only be powered on completion of all electrical and hydraulic works..

WARNING:

 

Using the water piping to earth the unit is 

not permitted.

WARNING:

 

Verify that all terminals are tight on power 

carrying conductors before first start-up 

and 30 days after putting into service. 

Afterwards check twice yearly.

 

Loose terminals can result in overheating 

of cables and components..

TABLE OF ELECTRICAL DATA

SIZE

 ANL

Po

w

er

 supply

Compr

essor

s [n

°]

Fans

 [n

°]

TOTAL INPUT

RECOMMENDED CABLE CROSS SECTION for 50 m max length

L.R.A.

L.R.A.

(Soft 

Start)

F.L.A. 

(w/o 

pumps)

SEZ. A

SEZ. B

EARTH 

(PE)

IL

[A]

[A]

[A]

phases

[n°]

cables 

per phase 

[n°]

cross sec-

tion 

[mm

2

]

total 

cables 

[n°]

[mm

2

] [mm

2

] [A]

290

400V/3N/50Hz

2

4

130

99

47.1

3+N

1

10

5

1

10

63

300

400V/3N/50Hz

2

4

131

101

50.3

3+N

1

10

5

1

10

63

340

400V/3N/50Hz

2

4

162

123

56.0

3+N

1

16

5

1

16

80

400

400V/3N/50Hz

2

6

183

140

65.9

3+N

1

16

5

1

16

100

580

400V/3N/50Hz

2

2

262

198

84.8

3+N

1

25

5

1

16

125

620

400V/3N/50Hz

2

2

308

230

99.1

3+N

1

35

5

1

16

125

650

400V/3N/50Hz

2

2

320

242

111.7

3+N

1

35

5

1

16

160

L1

L2

    L3 

     N

PE

400V/3N/50Hz

The ANL units are fully factory wired and only require 

connection to the power supply network, downstream 

of an isolator, in accordance with the applicable wiring 

standards of the country of installation. 

It is recommended to check the following items:

1. 

The electrical network is capable of meeting the 

electrical input data shown in the table below.

2. 

The unit is only powered up on completion of 

any hydraulic and electrical works.

3. 

Comply with the indicated phasing and earth 

requirements.

4. 

The power supply cable must have the appropri-

ate protection against short circuits, residual 

current and earth leakage with suitable isolation 

from other devices.

5. 

The tolerance on the power supply voltage is 

±10% of the nominal voltage rating of the unit 

(for three phase units a maximum imbalance of 

3% between phases is permitted). If these values 

are not met please contact the power supply 

company. 

6. 

For the electrical connections use double insu-

lated cables in accordance with applicable wiring 

standards.

MANDATORY REQUIREMENTS

1. 

A magneto-thermal circuit breaker conforming 

to IEC-EN standards (contact aperture minimum 

3 mm) is required, with adequate protection in 

accordance with the data provided in the follow-

ing table, to be installed as close as possible to 

the unit.

2. 

An effective earth connection is required. The 

manufacturer cannot be held responsible for 

any damages caused by lack of, or inadequate, 

earthing of the unit.

3. 

For three phase units check the correct cable 

phasing. 

The cable cross sections shown in the following cable 

are the recommended values based on a maximum 50 

m cable length.

For longer cable lengths or different types of cable 

installations, the DESIGNER is responsible for correctly 

sizing the isolator, circuit breaker, earthing protection 

and cable sizes, based on:

• 

Length

• 

Type of cable 

• 

Electrical input of the unit, distance and operat-

ing ambients.

8.1.  ELECTRICAL POWER SUPPLY CONNEC-

TIONS

1. 

Before making the electrical connections 

ensure that the isolator is open.

2. 

Open the front control panel.

3. 

Use the holes provided in the lower part of the 

cabinet for the electrical power supply and for 

other external wiring connections.

4. 

Enter cables into the control panel only through 

the apertures provided.

5. 

Avoid direct contact with un-insulated copper 

tubes and compressors. 

6. 

Identify the terminals for electrical connection 

with reference to the wiring diagram provided 

loose with the unit.

7. 

Take the power cable into the control panel and 

connect to terminals U-N and PE with respect 

LEGEND:
F.L.A.: 

Maximum current input

L.R.A.: 

Starting current

Sez A: 

Power supply connection

3+N:

3 phase + neutral

Sez B: 

C safeties connection

EARTH:

Earth connection to the unit

IL: 

Main isolator

• Hole for cable route.

• Hole for cable route.

Содержание Variable Multi Flow ANL 290

Страница 1: ...BARCODE EN Installation and Maintenance Manual CHILLERS EXTERNAL UNITS HIGH EFFICIENCY ANL 290 650 18 03 5719210_03...

Страница 2: ...es In addition the applied mark guarantees that our appliances fully comply with the safety requirements defined by the applicable product s rules We constantly monitor the quality level and as a resu...

Страница 3: ...EN 60335 2 40 A2 2009 CEI EN 55014 1 2017 CEI EN 60335 2 40 A13 2012 CEI EN 55014 2 2016 La presente dichiarazione di conformit rilasciata sotto la responsabilit esclusiva del fabbricante This declara...

Страница 4: ...7 3 Dimensions ANL 580 620 650 mm 15 7 4 Position of hydraulic connections mm 16 7 5 ANL C 290 300 340 400 mm 17 7 6 ANL C 580 620 650 mm 17 8 Electrical connections 18 8 1 Electrical power supply con...

Страница 5: ...h the equipment as this could result in accidents for which the manufacturer will not be held responsible The warranty will be voided if the above mentioned warnings are not respected 1 2 SAFETY INSTR...

Страница 6: ...ifting capability of the equipment being used taking into account the information provided with the packaging When lifting insert through the unit s base holes lifting bars NOT PROVIDED of sufficient...

Страница 7: ...nnection to the unit This clean ing eliminates welding slag dirt rust or any other impurities from the piping These impurities may otherwise be deposited within the unit and cause a malfunction The co...

Страница 8: ...freezing 1 Complete draining of water from the unit 2 Operating with glycol with a percentage of glycol se lected in accordance with the minimum anticipated external temperature 3 Use of electric hea...

Страница 9: ...ly sized for the required flow rate The water flow rate through the heat exchanger must always be constant WARNING Carefully clean the system prior to connection to the unit This clean ing eliminates...

Страница 10: ...must always be constant WARNING Carefully clean the system prior to connection to the unit This clean ing eliminates welding slag dirt rust or any other impurities from the piping These impurities ma...

Страница 11: ...heat exchanger must always be constant WARNING Carefully clean the system prior to connection to the unit This clean ing eliminates welding slag dirt rust or any other impurities from the piping Thes...

Страница 12: ...217 2 28 75 221 6 21 32 164 4 21 76 167 7 VT17 12 0 0 6 ANL 400 L P2 797 754 1049 536 52 805 1080 542 27 56 220 5 28 37 226 9 21 72 173 7 22 35 178 8 VT17 12 0 0 6 ANL 400 L P3 778 735 1032 537 54 788...

Страница 13: ...25 1160 1100 800 800 800 1100 3000 A Gy Gx B C D 1610 40 16 16 16 16 40 420 420 2050 200 200 2050 200 200 20 20 1060 7 1 DIMENSIONS ANL 290 300 340 mm 7 1 1 MAXIMUM OVERALL mm 1610 40 16 16 16 16 40 4...

Страница 14: ...0 16 16 16 16 40 420 420 2050 200 200 2050 200 200 20 20 1060 7 2 2 LIFTING POINTS mm 16 16 16 16 2050 200 200 2050 200 200 20 20 1060 7 2 3 POSITION ANTI VIBRATION MOUNTS mm 1605 1735 2450 2525 1160...

Страница 15: ...IMUM OVERALL mm 1875 3200 3275 2005 1100 1160 800 800 800 1100 3000 40 16 16 16 16 16 16 40 1525 1275 200 200 1525 1275 200 200 Gy Gx 1956 40 16 16 16 16 16 16 40 644 600 1525 1275 200 200 1525 1275 2...

Страница 16: ...UT 2 IN 2 195 180 670 ANL 290 300 340 400 VERSION 00 ANL 290 300 340 400 VERSION 01 02 03 04 P1 P2 P3 P4 IN 2 OUT 2 IN 2 OUT 2 205 180 492 205 180 670 IN 2 OUT 2 IN 2 OUT 2 IN 2 OUT 2 205 180 492 195...

Страница 17: ...ANL 290 650 EN 7 5 ANL C 290 300 340 400 mm 7 6 ANL C 580 620 650 mm 191 184 152 233 189 183 138 219 A C B D 189 183 138 219 C D A Inlet Intake line 35 B Otlet Liquid line 22 C Inlet Intake line 42 D...

Страница 18: ...e below 2 The unit is only powered up on completion of any hydraulic and electrical works 3 Comply with the indicated phasing and earth requirements 4 The power supply cable must have the appropri ate...

Страница 19: ...ct functioning of any flow switch installed close the isolating valve on the evaporator outlet and observe the result on the unit display panel open the valve and reset the flow trip alarm 9 3 FIRST S...

Страница 20: ...t the control panel is off WARNING For the installation refer to the electrical wiring schematics provide with the unit The electrical wiring schematic and manuals must be carefully conserved and made...

Страница 21: ...n and energy efficiency The fundamental required annual checks are 11 1 HYDRAULIC CIRCUIT CHECK 1 Water circuit is filled 2 Water filter is clean 3 Operation of the differential pressure or flow switc...

Страница 22: ...vents and of the terminal units 14 5 UNIT DRAINING WARNING During the winter period the water in the heat exchanger may freeze when the system is off causing irreversible damage to the heat exchanger...

Страница 23: ...installed PR3 Not installed Go to question 3 Installed Enter in parameter PAN index 9 menu INSTALLER with the appropriate value Value 1 Season selection controlled from the chiller circuit board ON OF...

Страница 24: ...ns loose Operating outside of limits Check against operating limits chart Pressostat faulty Replace the component Thermal cut out operates Check voltage and settings Check insulation of windings Compr...

Страница 25: ...02 04 P2 P4 9 Liquid sight glass 10 Desuperheater optional 11 Water filter 12 Pump s optional 13 Expansion tank standard with hydronic module 14 Buffer tank optional 15 Flow switch 16 Gauge 17 Air ven...

Страница 26: ...nal valve only for versions 02 04 P2 P4 9 Liquid sight glass 10 Desuperheater optional 11 Water filter 12 Pump s optional 13 Expansion tank standard with hydronic module 14 Buffer tank optional 15 Flo...

Страница 27: ......

Страница 28: ...C S p A Via Roma 996 37040 Bevilacqua VR Italia Tel 39 0442 633111 Fax 39 0442 93577 marketing aermec com www aermec com Aermec reserves the right to make all modification deemed necessary for improvi...

Отзывы: