Minimum average water temperature
If the fan coil is working in continuous
cooling mode in an environment
where the relative humidity is high,
condensate might form on the air
delivery and on the outside of the
device. This condensate might be
deposited on any objects underneath
and on the floor.
To avoid condensate on the external
structure of the device while the fan is
functioning, the average temperature
of the water must not be lower than
the limits shown in the table below,
that depend on the thermo-hygrometric
conditions of the air in the room.
These limits refer to unit operating with
fan at minimum speed.
Minimum average water temperature [°C]
Temperature of the air in the room with dry bulb
21
23
25
27
29
31
Temperature with wet bulb
of the air in the room
15
3
3
3
3
3
3
17
3
3
3
3
3
3
19
3
3
3
3
3
3
21
6
5
4
3
3
3
23
-
8
7
6
5
5
Pressure drops
Air flow rate
Output
C O R R E C T I O N F A C T O R S W H E N O P E R A T I N G U S I N G L Y C O L W A T E R
Key:
0,8
0,9
1,0
1,1
1,2
6
7
8
9
10
11
12
13
14
15
16
17 °C
Medium glycol water temperature
Correction factor
GLYCOL WATER AT 10%
GLYCOL WATER AT 35%
GLYCOL WATER AT 20%
IN THE COOLING OPERATION
IN THE HEATING OPERATION
0,6
0,7
0,8
0,9
1,0
1,1
1,2
6
7
8
9
10
11
12
13
14
15
16
17 °C
Medium glycol water temperature
Correction factor
0,5
0,6
0,7
0,8
0,9
1,0
1,1
1,2
1,3
1,4
1,5
1,6
6
7
8
9
10
11
12
13
14
15
16
17
18 °C
Medium glycol water temperature
Correction factor
30
40
50
60
70
80
90 °C
0,8
0,9
1,0
1,1
1,2
1,3
1,4
Medium glycol water temperature
Correction factor
0,8
0,9
1,0
1,1
1,2
1,3
1,4
30
40
50
60
70
80
90 °C
Medium glycol water temperature
Correction factor
0,8
0,9
1,0
1,1
1,2
1,3
1,4
30
40
50
60
70
80
90 °C
Medium glycol water temperature
Correction factor