36
HL C DIPSWITC
H CONFIGURATION
Sw 1
Sw 2
ON
OFF
DIPSWITCH CONFIGURATION
Configuration of dipswitches must only be carried out by qualified personnel during unit installation.
Always disconnect the power supply before performing this operation.
Adjust the dipswitches inside the thermostat for the following functions:
Sw 1
Dipswitch 1
(Default OFF)
Thermostatic temperature control:
- for operation at modulated power, set to OFF
- for 3-level operation, set to ON
Dipswitch 2
(Default OFF)
Adjustment band:
- for standard, set to OFF
- for extended, set to ON
Dipswitch 3
(Default OFF)
Louver control:
- for manual control, set to OFF
- for motorised control, set to ON
Dipswitch 4
(Default OFF)
Probe correction:
- for dynamic correction of values, set to OFF
- for fixed correction of values (heating mode 4°C), set to ON
Dipswitch 5
(Default OFF)
Enable heating mode according to water temperature:
- for normal heating mode (39°C), set to OFF
- for reduced Heating (35°C), set to ON
Dipswitch 6
(Default OFF)
Enable cooling mode according to water temperature:
- for normal cooling mode (17°C), set to OFF
- for reduced cooling (22°C), set to ON
Sw 2
Dip 1
(Default OFF )
Valve set up:
-set up without valve (Y1), OFF
-set up with valve (Y1), ON
Dip 2
(Default OFF )
Valve activation:
-Heating/Cooling valve activation (Y1), OFF
-Preset in factory
Dip 3
(Default OFF)
Preset in factory
Dip 4
(Default OFF)
Preset in factory
*
*
*
*
*
*
=
*
ON
OFF
1
2
3 4
5
6
*
*
*
*
ON
OFF
1
2
3 4
Sw 1
Sw 2
Thermostatic control with Modulated Power
Normal regulation band
Normal Cooling Enabling (water 17°C)
Normal Heating Enabling (water 39°C)
Dynamic Probe Correction
Manual slat management
Factory setting
Factory setting
Factory setting
System without cut off valve VCH
System with cut off valve VCH
Wide regulation band
Motorised slat management
Fixed probe correction Warm (4°C)
Reduced Heating Enabling (water 35°C)
Reduced Cooling Enabling (water 22°C)
Three step thermostat control
Factory settings
Содержание Omnia HL 11 CM
Страница 28: ...28 ACCESSORIES DATA DRIP TRAY BC10 DRIP TRAY BC20 ...
Страница 40: ...40 INSTALLATION DIAGRAMS L N OMNIA HL ...
Страница 41: ...41 L N INSTALLATION DIAGRAMS OMNIA HL L L N OMNIA HL C ...
Страница 42: ...42 INSTALLATION DIAGRAMS L N OMNIA HL S L N OMNIA HL PC ...
Страница 47: ...47 ...
Страница 48: ......
Страница 49: ......