![AERMEC Omnia HL 11 CM Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/aermec/omnia-hl-11-cm/omnia-hl-11-cm_technical-and-installation-booklet_2862018022.webp)
22
0
5
10
15
20
25
30
35
40
45
50
0
100
200
300
400
500
600
700
800
900 1000 1100
Water flow [l/h]
The pressure drops in the charts above refer to an average water temperature of 10 °C. The following table shows the cor-
rections to apply to the pressure drops with a variation in average water temperature.
Average water temperature
°C
5
10
15
20
50
60
70
Correction factor
1,03
1
0,96
0,91
0,78
0,75
0,72
TAV.9
COIL PRESSURE DROP
Coil pressure drop (kPa)
HL 36
HL 26
HL 16
HL 11
Содержание Omnia HL 11 CM
Страница 28: ...28 ACCESSORIES DATA DRIP TRAY BC10 DRIP TRAY BC20 ...
Страница 40: ...40 INSTALLATION DIAGRAMS L N OMNIA HL ...
Страница 41: ...41 L N INSTALLATION DIAGRAMS OMNIA HL L L N OMNIA HL C ...
Страница 42: ...42 INSTALLATION DIAGRAMS L N OMNIA HL S L N OMNIA HL PC ...
Страница 47: ...47 ...
Страница 48: ......
Страница 49: ......