18
PERFORMANCE SPECIFICATIONS
Size
Notes
ver.
0550
Performance in cooling mode
Cooling capacity
(1)
A
kW
108.1
(1)
E
kW
103.5
Input power
A
kW
34.9
E
kW
36.3
EER
A
W/W
3.10
E
W/W
2.85
ESEER
A
W/W
4.10
E
W/W
4.06
Water flow heat exchanger
°
l/h
18646
L
l/h
17862
Head drops
°
kPa
32
L
kPa
30
Energy efficient
Eurovent Class
A
A
E
C
data 14511:2013 (Eurovent)
1 Evaporator water temperature (in/out) 12°C/7°C; Outdoor air temperature 35°C
GENERAL SPECIFICATIONS
Size
Notes
ver.
0550
Compressor
Type
scroll
Number
no.
2
Number of steps
no.
50%
Number of circuits
no.
1
Minimum step
%
Type of refrigerant
R410A
Refrigerant load
A
kg
12.5
E
kg
12.5
Oil type
Oil load
A
kg
9.34
E
kg
9.34
System side heat exchanger
Type
plates
Number
no.
1
Resistance
no./W
-
Connections with Grooved Joints
Diameter
A
Ø (in/out)
6''
E
Ø (in/out)
6''
Desuperheater Heat Exchanger
Type
plates
Number
no.
1
Resistance
no./W
Connection type
Connection diameter
Ø (in/out)
Standard Fans
Type
Axial
Number
A/E
no.
2
Air flow rate
A
m
3
/h
32000
E
m
3
/h
24000
Useful static pressure
Pa
-
Inverter Fans “J”
Type
Axial
Number
A/E
no.
2
Air flow rate
A
m
3
/h
32000
E
m
3
/h
24000
Useful static pressure
Pa
-
Sound data
Sound Power Level
A
dB(A)
85
E
dB(A)
82
Sound Pressure Level
A
dB(A)
53
E
dB(A)
50
Sound power level (calculated when cold)
Aermec determines sound power values in agreement with the Standard UNI EN ISO 9614-2, in compliance with that requested by Eu
-
rovent certification.
Sound pressure level,
at a distance of 10 m, for units in open field conditions on a reflective surface; non-binding value obtained from the sound power level
Содержание NRV 0550