![AERMEC NRP 0800 Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/aermec/nrp-0800/nrp-0800_technical-manual_2862067026.webp)
KEY
(1)
Check that highest installation is not higher than 55 metres.
(2) Ensure that lowest installation can withstand global pressure
in that position.
H max (1) = 55 m
H = 12.25 m
H
H = 0 m
Pt
ar = H / 1
0.2 + 0.3
Pt
ar = 1
.5 bar
Pt
ar = 1
.5 bar
H min (2)
ATTENTION
It is recommended to design systems with
high water content (minimum recommended
values shown in table), to limit:
1. The hourly number of inversions
between functioning modes.
2. Decrease in water temperature during
winter defrost cycles.
NRP
U.M.
800
900
1000
1250
1400
1500
1650
1800
Number of compressors
n°
4
4
4
4
4
4
4
4
Minimum water content admitted COLD SIDE
gal/ton
6,50
6,50
6,50
6,50
6,50
6,50
6,50
6,50
Minimum water content admitted the HOT SIDE
gal/ton
6,50
6,50
6,50
6,50
6,50
6,50
6,50
6,50
Recommended water content COOLING SIDE | HEATING SIDE
gal/ton
13,01
13,01
13,01
13,01
13,01
13,01
13,01
13,01
14. EXPANSION VESSEL CALIBRATION
14.1. EXPANSION VESSEL CALIBRATION
Standard pre-load pressure value of the
expansion vessel is
1,5bar/21,8PSI
, whereas
volume is 24 litres. Maximum pressure
6bar/87PSI
.
Calibration of the vessel must be regulated using
the maximum level difference (H) of the user (see
diagram) by using the following formula:
p (calibration) [bar] = H [m] / 10.2 + 0.3.
For example: if level difference (H) is equal to
20m/65,6ft
, the calibration value of the vessel will
be
2,3bar/33,4PSI
.
If calibration value obtained from formula is less
than
1,5bar/21,8PSI
(that is for H < 12.25), keep
calibration as standard.
15. MINIMUM WATER CONTENT
26
INRP260HzTY. 1312. 5806717_03