![AERMEC NRP 0800 Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/aermec/nrp-0800/nrp-0800_technical-manual_2862067020.webp)
A
B
C
D
E
Condenser utput
water temeprature
°C
35
40
45
50
55
°F
95
104
113
122
131
A
B
C
D
E
Condenser utput
water temeprature
°C
35
40
45
50
55
°F
95
104
113
122
131
11.4. HEATING CAPACITY AND INPUT
POWER
The heating capacity yielded and the input electrical
capacity in conditions other than
rated conditions are obtained by multiplying the
rated values (Ph, Pa) by the respective correction
coefficients (Ch, Ca).
The diagram allows you to obtain the correction
coefficients; corresponding to each curve,
the temperature of the hot processed water referred
to is reported, assuming a difference
in water temperature between the input and output
of the condenser equal to 5°C/10°F.
KEY
:
Ph
: Heating
capacity
Pa
: Input
power
Ch
: Heating capacity correction coefficient
Ca
: Input power correction coefficient
11.5. FOR
Δ
T DIFFERENT FROM THE RA
TED VALUE
For
Δ
t different from 5K, refer to Tab.
“
t DIFFERENT FROM NOMINAL (
t 5)”
for the cooling capacity and input power correction
factors.
11.6. FOULING FACTORS
The performance levels indicated in table: ”
FOUL
ING FACTOR K*M
2
/ W ”
refer to conditions with
clean tubes, with a fouling factor = 1. For values
different from the fouling factor,
multiply the values in the performance table by the
reported coefficients.
t DIFFERENT FROM NOMINAL (
t 5)
3
5
8
10
Heating capacity
0,99
1
1,01 1,02
Input power
1,01
1
0,98 0,96
0,7
0,8
0,9
1,0
1,1
1,2
1,3
E
D
C
B
A
Pa: TOTAL INPUT POWER
-15
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
-13 -11 -9 -7 -5 -3 -1 1
3
5
7
9 11 13 15 17 19 21 23 25 27 29 30
86
°C
°F
EXTERNAL AIR TEMPERATURE d.b.
Ca
:
INPUT
PO
WER
C
ORRE
CTION
C
OEFFICIENT
Pr
oduced w
at
er t
emper
atur
e
CONDENSER
Pa: TOTAL INPUT POWER
0,6
0,7
0,8
0,9
1,0
1,1
1,2
1,3
1,4
E
D
C
B
A
Ph: HEATING CAPACITY
-15
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
-13 -11 -9 -7 -5 -3 -1 1
3
5
7
9 11 13 15 17 19 21 23 25 27 29 30
86
°C
°F
0,5
Pr
oduced w
at
er t
emper
atur
e
CONDENSER
EXTERNAL AIR TEMPERATURE d.b.
Ch
: HE
ATING
CAP
A
C
ITY
C
O
RRE
C
TION
C
O
EFFICIENTS
Ph: HEATING CAPACITY
FOULING FACTOR [K*M2]/[KW] correction factors
0,018
0,05
0,1
Cooling capacity
1
0,987 0,967
Input power
1
0,987 0,967
20