![AERMEC NRP 0800 Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/aermec/nrp-0800/nrp-0800_technical-manual_2862067015.webp)
Model
0800
0900
1000
1250
1400
1500
1650
1800
ELECTRICAL DATA: 230V 3 60HZ POWER SUPPLY
Input current (cooling mode)
A
245
-
-
-
-
-
-
-
Input current (total recovery mode)
A
219
-
-
-
-
-
-
-
Input current (heating mode)
A
264
-
-
-
-
-
-
-
NO PUMP VERSION
LRA
A
571
-
-
-
-
-
-
-
MCA
A
309
-
-
-
-
-
-
-
MOP
A
371
-
-
-
-
-
-
-
Recommended fuse
A
350
-
-
-
-
-
-
-
DHW/SYSTEM LOW HEAD PUMPS
LRA
A
595
-
-
-
-
-
-
-
MCA
A
332
-
-
-
-
-
-
-
MOP
A
394
-
-
-
-
-
-
-
Recommended fuse
A
350
-
-
-
-
-
-
-
DHW/SYSTEM HIGH HEAD PUMPS
LRA
A
608
-
-
-
-
-
-
-
MCA
A
346
-
-
-
-
-
-
-
MOP
A
408
-
-
-
-
-
-
-
Recommended fuse
A
400
-
-
-
-
-
-
-
ELECTRICAL DATA: 460V 3 60HZ POWER SUPPLY
Input current (cooling mode)
A
114
121
129
162
184
206
223
240
Input current (total recovery mode)
A
99
106
112
142
162
183
198
212
Input current (heating mode)
A
122
130
135
173
193
213
227
242
NO PUMP VERSION
LRA
A
294
344
355
448
500
528
546
541
MCA
A
151
162
172
234
266
294
312
328
MOP
A
181
196
206
281
326
354
373
374
Recommended fuse
A
175
175
200
250
300
350
350
350
DHW/SYSTEM LOW HEAD PUMPS
LRA
A
305
356
366
462
516
544
567
561
MCA
A
163
173
184
248
281
309
333
348
MOP
A
192
207
218
295
342
370
393
394
Recommended fuse
A
175
200
200
250
300
350
350
350
DHW/SYSTEM HIGH HEAD PUMPS
LRA
A
312
363
373
468
522
550
581
576
MCA
A
170
180
190
254
288
316
347
362
MOP
A
199
214
224
301
348
376
408
409
Recommended fuse
A
175
200
200
300
300
350
400
400
ELECTRICAL DATA: 575V 3 60HZ POWER SUPPLY
Input current (cooling mode)
A
88
94
100
126
143
160
173
186
Input current (total recovery mode)
A
37
82
86
109
125
141
152
164
Input current (heating mode)
A
95
100
105
134
149
165
176
187
NO PUMP VERSION
LRA
A
233
282
285
383
400
432
439
460
MCA
A
134
136
139
193
230
262
268
270
MOP
A
160
164
166
232
285
317
323
309
Recommended fuse
A
150
150
150
225
250
300
300
300
DHW/SYSTEM LOW HEAD PUMPS
LRA
A
242
291
294
394
413
445
455
476
MCA
A
143
145
148
204
242
275
285
287
MOP
A
170
173
176
243
297
330
340
325
Recommended fuse
A
150
150
175
225
250
300
300
300
DHW/SYSTEM HIGH HEAD PUMPS
LRA
A
248
297
299
399
417
450
466
488
MCA
A
149
151
154
209
247
280
296
298
MOP
A
175
178
181
248
302
335
351
337
Recommended fuse
A
175
175
175
225
300
300
350
300
15