MACHINE PURPOSE
The fan coil is a room air treatment terminal unit for both winter and summer operation.
DESCRIPTION OF THE UNIT
AVAILABLE SIZES
FCXI_AS
: without control panel and with Inverter motor, 3-row
heat exchanger, high cabinet for vertical installation, varnished
with anti-corrosion polyester powder (colour RAL 9002). The
delivery grille and the feet for floor-standing solutions (ZX ac-
cessory) are made of plastic of the colour RAL 7044. Requires
external control panel (accessory).
5 sizes
with 3-row coil
FCXI
20
AS
FCXI
30
AS
FCXI
40
AS
FCXI
50
AS
FCXI
80
AS
The FCXI_AS fan coils are available in:
5 sizes
with 3-row coil
FCXI 20 U
FCXI 30 U
FCXI 40 U
FCXI 50 U
FCXI 80 U
The FCXI_U fan coils are available in:
FCXI_U
: without control panel and with Inverter motor, 3-row
heat exchanger, universal cabinet for vertical fl oor-standing in-
stallation or wall-mounting, varnished with anti-corrosion pol-
yester powder, colour RAL 9002. The air delivery and suction
grilles are made using plastic material in colour RAL 7044.
Requires external control panel (accessory).
FCXI 20U ÷ 50U
FCXI 80U
TECHNICAL DATA AND OPERATING LIMITS
Minimum average water temperature
If the fan coil is working in continuous
cooling mode in an environment
where the relative humidity is high,
condensate might form on the air
delivery and on the outside of the
device. This condensate might be
deposited on any objects underneath
and on the floor.
To avoid condensate on the external
structure of the device while the fan is
functioning, the average temperature
of the water must not be lower than
the limits shown in the table below,
that depend on the thermo-hygrometric
conditions of the air in the room.
The limits mentioned above refer to
operation while the fan is set to its
minimum speed level.
In the event of prolonged fan inactivity
and with cold water passing through
the coil, condensate may form on the
external case of the unit.
As a result,
we recommend including the 3-way
valve accessory.
Water temperature
In order to prevent air stratification in
the room, and therefore to achieve
improved mixing, it is advisable not
to supply the fan coil with water at a
temperature over 65°C.
The use of water at high temperatures could
cause squeaking due to the different
thermal expansions of the elements
(plastic and metal), this does not however
cause damage to the unit if the maximum
operating temperature is not exceeded.
FCXI
20
30
40
50
80
Maximum water inlet temperature
°C
80°
Maximum recommended water inlet temperature
°C
65°
Maximum operating pressure
bar
8
Minimum water flow rate
l/h
100
100
150
150
300
Maximum water flow rate
l/h
750
750
1100
1150
2200
Room temperature limits (Ta)
°C
0° < Ta < 40°
Relative humidity limits in the room (R.H.)
R.H. < 85%
Power supply
230 V ( ±10% ) ~ 50 Hz
Performance values refer to the following conditions:
- at the maximum motor speed;
- the total input power is determined by adding the input power
for the unit and the input power for the accessories connected
and declared in the corresponding manuals.
MINIMUM AVERAGE WATER TEMPERATURE [°C]
Dry bulb ambient air temperature
21
23
25
27
29
31
Wet bulb ambient
air temperature
15
3
3
3
3
3
3
17
3
3
3
3
3
3
19
3
3
3
3
3
3
21
6
5
4
3
3
3
23
-
8
7
6
5
5