Minimum average water temperature

If the fan coil is working in continuous 

cooling mode in an environment 
where the relative humidity is high, 
condensate might form on the air 
delivery and on the outside of the 
device. This condensate might be 
deposited on any objects underneath 
and on the floor. 

To avoid condensate on the external 

structure of the device while the fan is 
functioning, the average temperature 
of the water must not be lower than 
the limits shown in the table below, 
that depend on the thermo-hygrometric 
conditions of the air in the room. 

The limits mentioned above refer to 

operation while the fan is set to its 

minimum speed level. 

In the event of prolonged fan inactivity 

and with cold water passing through 
the coil, condensate may form on the 
external case of the unit.

 As a result, 

we recommend including the 3-way 
valve accessory.

Water temperature

In order to prevent air stratification in 

the room, and therefore to achieve 
improved mixing, it is advisable not 

to supply the fan coil with water at a 
temperature over 149°F / 65°C. 

The use of water at high temperatures could 

cause squeaking due to the different 

thermal expansions of the elements 

(plastic and metal), this does not however 
cause damage to the unit if the maximum 
operating temperature is not exceeded.

Performance values refer to the following conditions:
- at the maximum motor speed;

- the total input power is determined by adding the input power 

for the unit and the input power for the accessories connected 
and declared in the corresponding manuals.

OPERATING LIMITS

FCXI

20 /220US 30 /220US 40 /220US 50 /220US 80 /220US
24 /220US 34 /220US 44 /220US 54 /220US 80 /220US

Maximum water inlet temperature

176°F / 80°C

Maximum recommended water inlet temperature

149°F / 65°C

Maximum operating pressure

115psi / 8bar / 

Room temperature limits (Ta)

32°F < Ta < 113°F / 0°C < Ta < 45°C

Relative humidity limits in the room (R.H.)

U.R. < 85%

Power supply

220V ( ±10% ) ~ 60Hz

 MINIMUM AVERAGE WATER TEMPERATURE  

[°F/°C]

Dry bulb ambient air temperature

70/21

73/23

77/25

80/27

84/29

88/31

Wet bulb ambient 

air temperature 

59 / 15

37.4/3

37.4/3

37.4/3

37.4/3

37.4/3

37.4/3

62.6 / 17

37.4/3

37.4/3

37.4/3

37.4/3

37.4/3

37.4/3

66.2 / 19

37.4/3

37.4/3

37.4/3

37.4/3

37.4/3

37.4/3

69.8/21

48.2/6

41/5

39.2/4

37.4/3

37.4/3

37.4/3

73.4/23

-

46.4/8

44.6/7

48.2/6

41/5

41/5

Water flow limits for 3-row coil

FCXI

20 /220US

30 /220US

40 /220US

50 /220US

80 /220US

Minimum water flow

l/h

100

100

150

150

300

gpm

0.44

0.44

0.66

0.66

1.32

Maximum water flow

l/h

750

750

1100

1100

2200

gpm

3.3

3.3

4.84

4.84

9.68

Water flow limits for 1-row coil

FCXI

20 /220US

30 /220US

40 /220US

50 /220US

80 /220US

Minimum water flow

l/h

50

50

50

50

100

gpm

0.22

0.22

0.22

0.22

0.44

Maximum water flow

l/h

400

400

400

400

900

gpm

1.76

1.76

1.76

1.76

3.96

Water flow limits for 4-row coil

FCXI

24 /220US

34 /220US

44 /220US

54 /220US

84 /220US

Minimum water flow

l/h

150

150

150

150

300

gpm

0.66

0.66

0.66

0.66

1.32

Maximum water flow

l/h

1100

1100

1100

1100

2200

gpm

4.84

4.84

4.84

4.84

9.68

Содержание FCXI 20 / 220 US

Страница 1: ...XI 80 220 US FCXI 24 220 US FCXI 34 220 US FCXI 44 220 US FCXI 54 220 US FCXI 84 220 US FAN COIL WITH INVERTER VENTILO CONVECTEUR AVEC INVERTER U S E A N D I N S TA L L AT I O N M A N UA L MANUEL D UT...

Страница 2: ......

Страница 3: ...ation de l unit Raccords hydrauliques Raccords d vacuation des condensats 16 Raccordements lectriques Rotation de la batterie 17 Dimensions 18 Schemas electriques 23 Solution des problemes 24 R glages...

Страница 4: ...not in any case cover costs due to automatic ladders scaffolding or other lifting systems neces sary for carrying out repairs under guarantee AERMEC S p A declines all responsibility for any damage wh...

Страница 5: ...order SUPPLEMENTARY CLEANING The fact that the blades of examinable shrouds can be removed operation done only by adequately skilled technicians ensures a thorough cleaning of the internal components...

Страница 6: ...total input power is determined by adding the input power for the unit and the input power for the accessories connected and declared in the corresponding manuals OPERATING LIMITS FCXI 20 220US 30 220...

Страница 7: ...nate current motors the brushless electric motor offers huge advantages Reduced wear and tear The possibility to regulate the rotation speed in a precise continuous manner 0 100 Higher energy yields L...

Страница 8: ...he oil vapours mixed with the treated air can be deposited on the exchange coils reducing their performance or on the parts inside the unit damaging the plastic parts If a three way valve is installed...

Страница 9: ...he relative chapter The fan coils that work in heat mode only do not require condensate discharge Make the electrical wiring as shown in the relative chapter and in the wiring diagrams Install and con...

Страница 10: ...th a minimum contact opening distance of 0 12inch 3mm The use of B type circuit breakers is recommended For installations with three phase power supply the following precautions should be considered 1...

Страница 11: ...1 97 1 97 1 97 1 97 Weight Poids lbs 33 07 34 17 44 09 45 19 52 91 54 01 52 91 54 01 74 96 75 06 Metric system Syst me m trique A mm 487 487 487 487 590 B mm 750 980 1200 1200 1320 C mm 220 220 220 2...

Страница 12: ...21 97 C 1 97 1 97 B A 35 x 0 79 15 28 8 50 1 61 3 98 1 93 5 67 1 77 3 35 1 18 1 18 8 50 3 78 2 36 7 76 17 83 17 83 0 98 FCXI 20 30 40 50 220US FCXI 24 34 44 54 220US FCXI 80 US FCXI 84 US 3 R 4 R 3 R...

Страница 13: ...8 B mm 522 753 973 1122 1122 C mm 440 671 891 891 1102 FCXI 20 30 40 50 220US FCXI 24 34 44 54 220US FCXI 80 220US FCXI 84 220US 3 R 4 R 3 R 1 R 3 R 4 R 3 R 1 R Metric system Syst me m trique FCXI 20...

Страница 14: ...ie femelle 3 4 F 3 4 F 3 4 F 3 4 F 3 4 F FCXI 20 220US 30 220US 40 220US 50 220US 80 220US 24 220US 34 220US 44 220US 54 220US 84 220US US measure system Syst me de mesure US inches A 15 91 15 91 15 9...

Страница 15: ...S 30 220US 40 220US 50 220US 80 220US BV1 BV1 BV1 BV1 BV1 US measure system Syst me de mesure US inches A 16 06 16 06 16 06 16 06 20 43 B 12 72 12 72 12 72 12 72 14 88 C 6 02 6 02 6 02 6 02 6 69 D 3 7...

Страница 16: ...ng Raccordements effectuer in situ AR Orange Orange BI White Blanc BL Blue Bleu GI Yellow Jaune GR Grey Gris MA Brown Marron NE Black Noir RO Red Rouge VE Green Vert VI Violet Violet READING KEY LEGEN...

Страница 17: ...ure and humidity indica ted in MINIMUM AVERAGE WATER TEMPERATURE have been reached On a atteint les conditions limite de temp rature et d humidit indiqu es dans TEMPERATURE MINIMA LE MOYENNE DE L EAU...

Страница 18: ...FCXI84 220US WARNING Do not modify the unit s settings Any change to the inverter card dip switch settings may cause damage to the unit For this reason the diagram of the factory settings are indicat...

Страница 19: ......

Страница 20: ......

Страница 21: ...erve le droit de modifier tous moments les donn es consid r es n cessaires l amelioration du produit Technical data shown in this booklet are not binding Aermec S p A shall have the right to introduce...

Отзывы: