AERMEC DUALJET 20 Скачать руководство пользователя страница 16

I

taliano

29

IDJULJ 1207 - 6339500_00

THERMOSTAT TECHNICAL CHARACTERISTICS (E0) 

Power 

/-10%, 50-60 Hz

Max Absorbed Power (excluding TRIAC controlled 
loads) 

2.5VA

Digital Inputs 

N°2 dry contacts

Analogue Inputs

N°2 for sensors NTC 10K

Digital Outputs 

N°5, 230Vac Triac

Mounting Unit 

mounted

Protective Rating 

IP20 (referring to plastic containment)

Storage conditions 

-20 to 80°C, relative humidity 80% non condensing

Operating conditions

0 to 50°C, relative humidity 80% non condensing

Software class 

Class A

Outputs: Fan control

Voltage

230Vac

Maximum current

0.7A

THERMOSTAT CONNECTIONS SPECIFICATIONS (E0)

Power 

Screw terminals sized  5mm
Cable section min=0.5mm

2

 max=2.0mm

2

Accessory control outputs (Valves-Plasmacluster germi-
cide lamp, etc…)

Screw terminals sized  5 mm
Cable section min=0.5mm

2

 max=1.3mm

2

Max cable length = 30m

Digital Input CE 

Screw terminals sized  3.81mm
Cable section min=0.2mm

2

  max=1.0mm

2

Max cable length = 100m

Digital Input MS Sweeping contact 

Max cable length = 3m

Analogue Inputs (SA-SW) 

Quick insertion connection
Max cable length = 3m

Local serial TTL 

Screw terminals sized  3.81mm
Cable section min=0.2mm

2

  max=1.0mm

2

Max cable length = 30m

Содержание DUALJET 20

Страница 1: ...MANDATA CONTROLLATA Manuale installazione CONTROLLED OUTLET FAN COIL Installation Manual VENTILO CONVECTEURS REFOULEMENT CONTR L Manuel d installation GEBL SEKONVEKTOREN MIT KONTROLLIERTER ZULUFT Inst...

Страница 2: ...service apr s vente de votre secteur Lors de l installation de l appareil il faut pr voir l espace n cessaire pour les op rations d entretien et ou de r paration La garantie de l appareil ne couvre p...

Страница 3: ...e seguenti direttive Direttiva Bassa Tensione LVD 2006 95 CE Direttiva Compatibilit Elettromagnetica EMC 2004 108 CE Direttiva Macchine 2006 42 CE DUALJET CON ACCESSORI E fatto divieto di mettere in s...

Страница 4: ...tieren wenn sein Gewicht die 25kg bersteigt NO transportar la m quina solos si su peso es superior a los 25Kg NON lasciare gli imballi sciolti durante il trasporto Non rovesciare DO NOT leave boxes un...

Страница 5: ...0 Versions Thermostat Description of functions 21 Control of 2 pipe systems 22 TTL network settings Installation information 23 Installation of the unit 24 Rotating the coil 26 Connections 27 Dip Swit...

Страница 6: ...re is exceeded MAINTENANCE DO NOT USE TOO HOT WATER Use a soft cloth or sponge with water at a maximum of 40 C to clean the fan coil unit Do not use chemical products or sol vents on any parts of the...

Страница 7: ...air is directed towards the ceiling The user can decide at any moment where to direct the flow of air Low noise operation The extremely low noise ventilation take the Aermec fan coil units to the pinn...

Страница 8: ...es Control on temperature air side Whenever the measured ambient tem perature is below the set point by a value equal to the Dead band the unit operates in Heating mode Whenever the measured ambient...

Страница 9: ...the speed V1 V2 and V3 The fan is cycled on off at the selected velocity Automatic with selector in AUTO position The speed of the fan is con trolled as a function of the ambient conditions and the c...

Страница 10: ...ter Sensor Present Water Sensor Absent With Valve Pre heating delayed Pre heating delayed No Ventilation delay Pre heating delayed Minimum and maximum controls active No minimum or maximum control Min...

Страница 11: ...ical isolator or plug that allows the electrical power to be completely isolated from the unit WARNING The unit is connected to the power supply network Any intervention by personnel not technically q...

Страница 12: ...on the side of the frame connections side To install the unit proceed as follows Remove the casing by unscrewing the screw For wall mounting use expansion plugs not provided as shown in the diagram Ca...

Страница 13: ...e right side rotate the coil and fix with the screws previously removed refit the cover and fix with the screws mount the plastic caps supplied loose into the holes left empty by the hydraulic connect...

Страница 14: ...the control panel Ensure that all connections and their cables are correctly fixed Run cables so that they cannot suffer cuts crushing jerking abrasion and damage in general Ensure that the board s f...

Страница 15: ...or upstream of control valve Dip 3 Default OFF Ventilation control OFF Thermostatic ventilation ON Continuous ventilation Dip 4 Default OFF Ventilation enabling OFF Enabling normal range ON Enabling r...

Страница 16: ...ng Software class Class A Outputs Fan control Voltage 230Vac Maximum current 0 7A THERMOSTAT CONNECTIONS SPECIFICATIONS E0 Power Screw terminals sized 5mm Cable section min 0 5mm2 max 2 0mm2 Accessory...

Страница 17: ...eichen der maximalen Temperatur und Feuchtigkeitswerte siehe Abschnitt DURCHSCHNITTLICHE MINDEST WASSERTEMPERATUR Se han alcanzado las condiciones l mites de temperatura y humedad descritas en M NIMA...

Отзывы: