background image

13

3. 

The function remains active even when the unit has been switched off. To deactivate it, set “Weather 
depend: Off manually.”;

4. 

In the “View” menu, you can see the target value of the climatic curve.

5. 

The function can still be set if the unit is OFF, but it will only be implemented if the unit is activated.

6. 

If the relative function is activated (paragraph 8.3), the value of this parameter will be stored in the 
memory and automatically reset after any possible voltage failure.

7. 

The default value for this function is “Off”.

After accessing the “Weekly timer” function, you can 
set up to three time bands for each single day of the 
week; during these time bands, the unit will work with 
the current mode and set-point. Alternatively, you 
can assign the “Holiday” value to one day or more; if 
the specific “Holiday program“ function is enabled, an 
operating set-point of 30°C will be automatically set 
if you use the check on the delivery water, or 10°C if 
you use the ambient air check (installing the specific 
air probe accessory).

Clicking on the label for one of the days of the week 
allows access to the page for that day, where you can 
assign a value to the day, including:
• 

“With” = if the Weekly Timer is active, the system 
will perform the programmed access as speci-
fied in the data for periods 1, 2 and 3

• 

“Without” = the Weekly Timer is also active, this 
day will not be considered

• 

“Holiday“ = if the “Holiday release” is active, dur-
ing this day the set will be kept at 30°C (for water 
control) or 10°C (for air control)

• 
By clicking on the label for one of the periods during 
the selected day, you can access the period settings 
page. The possible period settings are:
• 

“With” = the period describes a time band when 
the unit is to be used;; in this case, the labels re-
lating to the start and end times for the period 
will also be displayed (which will be set first by 
clicking on the time label to be set and then 
sliding your fingertip over the time values until 
you select the ones required; lastly, press the top 
right button to save the data entered)

• 

“Without” = the period will not be used

4.8. 

Setting a timer for programmed switch-on and/or switch-off (Weekly timer

 

)

Weekly timer

Weekly timer: On

Mon: Valid

Tue: Invalid

Wed: Invalid

Thur: Invalid

Fri: Invalid

Sat: Holiday

Sun: Holiday

Mon

Mon: Valid

Period 1: Invalid

Period 2: Invalid

Period 3: Invalid

00 00
01 01
02 02

23 59

22 58

Period 1

Period 1: Valid

Start Timer: 00:00

End Timer: 00:00

00 00
01 01
02 02

23 59

22 58

Period 1

Period 1: Valid

Start Timer: 00:00

End Timer: 00:00

Содержание BHP Series

Страница 1: ...USER MANUAL 6228081_03 2020 02 20 08 52 0 0 C 0 0 C 25 C EN HMI series BHP series...

Страница 2: ...administrative sanctions envisaged by the laws in force All specifications are subject to modification without prior notice Although every effort has been made to ensure accuracy Aermec cannot be held...

Страница 3: ...bling the Holiday Program function used for the weekly timer Holiday release 14 4 10 Enabling disabling the anti legionella cycle Disinfection 14 4 11 Setting a timed switch on switch off Clock timer...

Страница 4: ...mode forcing Force mode 33 7 15 Activating auxiliary device management Gate Ctrl 33 7 16 Setting of max absorption A P limit 33 7 17 Setting the serial address of the unit Address 34 7 18 Setting the...

Страница 5: ...pears on the display From this page it will be possible to select one of the menus available to the user turn on off the unit display information regarding the operating mode any active errors in addi...

Страница 6: ...end 4 7 Weekly timer 4 8 Holiday release 4 9 Disinfection 4 10 Clock timer 4 11 3 Temp timer 4 12 Emergen mode 4 13 Holiday mode 4 14 Preset mode 4 15 Error reset 4 16 4 Wifi reset 4 17 Reset 4 18 Pag...

Страница 7: ...eater 7 9 Ambient sensor 7 10 Air removal 7 11 3 Floor debug 7 12 Manual defrost 7 13 Force mode 7 14 Gate Ctrl 7 15 Current limit 7 16 4 Address 7 17 Refri recovery 7 18 Tank heater 7 19 Memory conta...

Страница 8: ...ill ask for con firmation of the switching on or off through another window where the on off command can be confirmed or cancelled 16 41 2017 05 04 Fri Function Parameter View Commission General 3 BAS...

Страница 9: ...navigating the menu pages the current page of the selected menu will be displayed in the header i e in the darker upper area 2 any functions not available will be highlighted by the letters NA Mode He...

Страница 10: ...t after any possible voltage failure 4 The default value for this parameter is Off 4 3 Activating the function for fast domestic hot water production Fast hot water After accessing the Cool hot water...

Страница 11: ...ock timer two keys will appear Use them to set the start and end of the Quiet mode acti vation period To set the values press the time label in question and set the hours and minutes by sliding the va...

Страница 12: ...page 2 Move on to the next page 3 Go back to the higher level menu 4 Go back to the main page Home To activate this function click on the Weather de pend label the first item on the first page of the...

Страница 13: ...he day including With if the Weekly Timer is active the system will perform the programmed access as speci fied in the data for periods 1 2 and 3 Without the Weekly Timer is also active this day will...

Страница 14: ...ry and automatically reset after any possible voltage failure 7 The default value for this function is Off Holiday release On O OK Cancel NB 1 if one day or more is set on Holiday in the weekly timer...

Страница 15: ...unit will produce a message on the screen to indi cate the anomaly This message can be reset by pressing OK 7 An anti legionella cycle will automatically be interrupted by any possible communication e...

Страница 16: ...button to save the data entered Click on the labels for parameters with numeric values to be inserted to display a numeric keypad with an indication of the range of permitted values which you can use...

Страница 17: ...to the value specified in the WOT heat 1 parameter which when clicked will display a numeric keypad to change its value Set Period 2 with related WOT heat 2 in the same way Click on the labels for th...

Страница 18: ...of Emergency mode in Heating will be blocked if the HP Water Switch Auxi heater 1 Auxi heater 2 Temp AHLW errors appear 5 The use of Emergency mode in DHW will be blocked if the Auxi WTH error appear...

Страница 19: ...atically reset after any possible voltage failure 6 The default value for this function is Off 4 14 Setting the winter period absence function Holiday mode This function is used to set one to four dai...

Страница 20: ...he dialogue box This function is used to reset the WiFi connection eliminating any conflicts This function is used to load the default values values pre set in the factory for all functions by resetti...

Страница 21: ...used in control based on delivery water 7 25 C WOT heat Indicates the operating set point for heating mode used in control based on delivery water 20 60 C RT Cool Indicates the operating set point for...

Страница 22: ...ad only Label Meaning Status Compressor Indicates the current status of the compressor On Off Fan Indicates the current status of the fan On Off Unit status Indicates the status of the unit Cool Heat...

Страница 23: ...ure detected by the unit T suction Indicates the temperature on the compressor inlet T discharge Indicates the compressor delivery temperature T Defrost Indicates the temperature for the defrosting cy...

Страница 24: ...r more information about the error codes refer to chapter 9 6 5 Viewing the error log Error log These pages display the version of the software installed on the unit 6 6 Viewing software information V...

Страница 25: ...ters will be stored in the memory and automatically reset after any possible voltage failure After accessing the Ctrl state function you can choose whether to base the unit control logic on the proces...

Страница 26: ...OK to confirm After accessing the Heat 2 Way valve function you can set the status of the 2 way valve in heating mode for more information about the assembly and use of the 2 way valve refer to the in...

Страница 27: ...NOTES 1 The available options depend on the settings associated with the production of domestic hot water presence of a compatible Aermec accessory tank etc 2 To change the thermostat settings the un...

Страница 28: ...he temperature measured by the outside air probe is lower than the Additional heat source temp parameter Heating the unit and its circulator will not be active the 3 way valve will be blocked on the s...

Страница 29: ...stem terminal side and the DHW side with water at the same temperature so the system side terminals must necessarily be fitted with mixer valves to ensure the hot inlet water is correctly managed 4 Th...

Страница 30: ...electric heaters 6 The electric heaters for the system and the electric heater in the DHW tank available as an Aermec accessory will never be activated simultaneously 7 If the relative function is act...

Страница 31: ...atically reset after any possible voltage failure 7 10 Setting the installation of the remote room temperature probe Ambient sensor Air removal Air Water tank O OK Cancel NOTES 1 This function can onl...

Страница 32: ...on 3 If the relative function is activated paragraph 8 3 the value of these parameters will be stored in the memory and automatically reset after any possible voltage failure Start Floor debug On Segm...

Страница 33: ...external contact for more information about this contact refer to the in stallation manual Make your selection then press OK to confirm Gate Ctrl On O OK Cancel NB 1 This function must only be activat...

Страница 34: ...tion is only useful only if tech nical maintenance intervention on the unit is re quired consequently it must only be activated by personnel authorised to provide technical assis tance and or install...

Страница 35: ...mec accessory tank via the heat pump only To set the required value use the and keys entering a value within the permitted range once the value has been set press the OK button to confirm it and retur...

Страница 36: ...lected menu will be displayed in the header i e in the darker upper area Click on the Temp unit label to change the unit of measurement used for temperature Celsius or Fahr enheit General 1 2 Temp uni...

Страница 37: ...c display switched off after 5 minutes of in activity press on the display to automatically switch it back on General 1 2 Temp unit Celsius On O memory On Beeper O Back light Lighter Time Date Enter 8...

Страница 38: ...S 1 The EWPE SMART app is compatible with ANDROID and iOS systems 2 The unit can only be managed via a WiFi or hotspot 4G signal 3 The system is compatible with routers that use WEP cryptography 8 8 A...

Страница 39: ...e sensor at heat exchanger plate outlet water side F9 Temp AHLW Indicates a fault on the temperature sensor located downstream of the 3 way valve if the installation includes an auxiliary electrical r...

Страница 40: ...icates a power supply error PP Temp driver Indicates an error affecting the external air sensor PF AC contactor Indicates a protection status on the power supply P9 Temp drift Indicates a protection s...

Страница 41: ......

Страница 42: ......

Страница 43: ...43...

Страница 44: ...el prodotto Aermec reserves the right to make all modifications deemed necessary for improving the product at any time with any modification of technical data SCARICA L ULTIMA VERSIONE DOWNLOAD THE LA...

Отзывы: