Fault
Code
LED Code
Error
Description
Recommended Action
-1051
-1052
Solid Red
Active Cooling
Degraded
Degraded active cooling
capability has been
detected.
Replace Fan Module.
-1102
8 Flashes -
Red
High Battery
Temperature
Detected
The battery temperature
sensor has detected a high
battery temperature.
Operating the battery at a
high temperature will greatly
reduce its lifespan.
Consider increasing the battery
temperature compensation
factor with the AERL Link
Software or reducing the
ambient environment
temperature.
-1103
9 Flashes -
Red
Low Battery
Temperature
Detected
The battery temperature
sensor has detected a low
battery temperature.
Operating the battery at a
low temperature may
greatly reduce its lifespan.
Consider a temperature-
controlled battery environment if
the battery regularly
experiences low temperatures.
-1401
-1402
-1403
10 Flashes -
Red
Earth Fault
Detected
An Earth Fault has been
detected.
Disconnect the device, confirm
the fault with a Megger, and
repair the system.