Wiring Information
This section will provide information and instructions for safely wiring up the DC connections on the CoolMax
SRX-R.
Wire and Disconnect Sizing
Use a minimum of #6 AWG (16 mm
2
) wire for the output between the backplane and the battery bus bar or
termination and use an appropriately sized insulated crimp ferrule when terminating both the input and
output connections.
Torque all CoolMax wire and ground terminals to 1.7 Nm (15 in-lb).
CoolMax SRX-R 450/55-48
•
The output current limit of the CoolMax SRX-R 450/55-48 is 55 amps.
•
Use a
63A
Non-Polarized DC
Circuit Breaker
between the controller output and load.
o
Recommended Option:
Beny BB1-63 63A 600V 2-Pole Circuit Breaker
CoolMax SRX-R 600/70-48
•
The output current limit of the CoolMax SRX-R 600/70-48 is 70 amps.
•
Use a
125A
Non-Polarized DC
Circuit Breaker
between the controller output and load.
o
Recommended Option:
Beny BD-125 125A 1000V 4-Pole Circuit Breaker
Please refer to the relevant IEC or AS/NZS electrical code for recommendations on PV array cable sizing,
length, and ampacity.
All devices connected to the controller must have suitable insulation in accordance with the relevant product
standards.
IMPORTANT
•
Wire sizes must comply with local and national standards. Input conductors and
circuit breakers must be rated at 1.56 times the short-circuit current of the PV array.
•
Copper wiring must be rated at 75°C or higher.