48
www.aerex.de
Reco-Boxx ZXR / ZXA / Flat – Operation and maintenance instructions
[03/
2021]
9.19 Type 18: Alarm indicating an incorrect position of the modulating bypass relative to
the ordered position
• Conditions:
• PX units with modulating bypass.
• Causes:
• This alarm indicates that the modulating bypass has not reached the ordered position within 10
seconds. The most common reason for this is a damaged position sensor on the bypass actua-
tor, and this must be replaced. Other reasons may be that the control board output is damaged,
implying the replacement of the board, or a mechanical blocking verified by a visual inspection of
the bypass.
• Effects:
Displayed on Touchpanel
Text displayed
LED ALARM
LED Pa
B.20
Position of the modulating bypass incorrect
RED
/
TAC5 control board
AL1 relay
O.R.1
LED ALARM
LED AF
Fans
Alarm Status
/
ON
/
Stopped
Manual reset mandatory.
9.20 Type 19: Alarm indicating that the hours limit for the maintenance of the filters has
been reached
• Conditions:
• The basic setup parameter “Filters Resets” must be >0.
• Causes:
• Alarm indicating that the hours limit for the maintenance of the filters has been reached.
• Effects:
Displayed on Touchpanel
Text displayed
LED ALARM
LED Pa
FILTERS ALARM
RED
/
TAC5 control board
AL1 relay
O.R.1
LED ALARM
LED AF
Fans
/
/
ON
/
/
Auto reset: via dedicated reset