Reco-Boxx ZXR / ZXA / Flat – Operation and maintenance instructions
[03/
2021]
Stop fan when pressure alarm
Possibility to stop the fans automatically in case of a pres-
sure alarm.
Setting
Settings range
Factory setting
Stop fans
No
Yes
No
Start torque
Possibility to change the fans’s starting torque.
Setting
Settings range
Factory setting
Start Torque
0...100 %
2 %
Deactivate softstop
With this function, the “OFF” function is deactivated.
Setting
Settings range
Factory setting
Softstop
Yes
No
No
Temperature
In this menu advanced temperature control parameters
can be modified.
Supply air
involves keeping a constant supply air temper-
ature without consideration to the load in the premises.
Extract air
involves keeping a constant temperature in the
extract air duct (premises), by modulating the supply air
temperature.
The reaction speed of capacity control signal can be mod-
ified. A higher Setting will result in a smoother control; a
lower Setting will result in a faster reaction speed. but also
greater risc of oscillations.
Setting
Settings range
Factory setting
Supply or Extract
temperature
control?
Supply
Extract
Supply
Reaction speed
1...10
1
Supply air, min.
0...20 °C
15,0 °C
Supply air, max.
16...50 °C
28,0 °C
Stop fan if T°Supply
<5°C
No
Yes
No