26 / 34
TF5814GB_E
Aereco S.A.
10.
VMX RELAY OUT MODULE
Offered as an option, the VMX Relay OUT module enables information to be communicated outside the system (status display, for example).
1
2
10.4. SETTINGS
92
35
58
10.1. FIELD OF APPLICATION
·VMX system
·unizone and multizone application
·Presence or motion or CO
2
type detection
10.2. DESCRIPTION
VMX Relay OUT module transmits the status of an element in the system. It is a contact which is
normally open but which closes when an event is detected.
Parameters for the triggering event can be configured (via the selector located on the module)
from amongst:
·signalling breakdown(s) in the system,
·signalling the correct functioning of the system,
·rate of ventilation (selection x minutes in units of 10 minutes),
·signalling a presence (time out 5 minutes),
·signalling a presence (time out 20 minutes),
·select when surpassing the CO
2
threshold (+0/-100 ppm), parameter on the VMX S-CO2 sensor,
·select when there is a peak flow demand,
·select when there is a minimum flow demand.
The Relay OUT module allows selection up to 500 mA under 24 VDC or 230 VAC.
Examples of applications: to light up a lamp the moment a presence is detected, to activate an
indicator to signal a breakdown in the system, etc.
The Relay OUT module is equipped with LEDs which indicate that it is operating and warn in case
of a breakdown in this module.
10.3. DIMENSIONS
2
Interpretation of sensor signals
BEHAVIOUR OF THE LEDS
Default
(fast)
(x4)
Closed
(flashes)
Open
(flashes)
(flashes)
INTERPRETATION
open
closed
system not configured
configuration change without new
memorisation of main module
a module or a sensor is not working correctly
To configure the module
1
Event selector switches
The revolving selector enables the selection of the event which will trigger a closed contact:
·0-1 : signalling breakdown(s) in the unit
·2-3 : signalling the correct functioning of the unit
·4-5 : rate of ventilation (selection x minutes / 10)
·6-7 : signalling a presence (time out 5 minutes)
·8-9 : signalling a presence (time out 20 minutes)
·10-11 : select when surpassing the CO
2
threshold (+0/-100 ppm)
·12-13 : select when there is a peak flow demand
·14-15 : select when there is a minimum flow demand
VMX Relay OUT Module