18 / 36
TF6400_A
Aereco S.A.
If using crimping tool to fit the RJ12 plug to the cable, be careful of the position of the wire at both
cable end: the wires must have the same order at both end as shown on the picture below.
Global electrical diagram
4.1. ELECTRICAL CONNECTION ON THE DXA UNIT
1
Sensor / Interface (RJ 12)
2
DX Hub (RJ 45 - not used in Premium
version)
3
Pump Alarm 9V (optional)
4
Alarm 9V (optional)
5
Defrosting control 9V (optional)
6
Compensation exhaust valve (RJ 45)
7
9VDC OUTPUT
8
230VAC, 50/60Hz, 180W max
9
ON / OFF
DXA Unit
1
2
3 4 5
+
-
+
-
7
6
9
To circuit
breaker 2A
N
GND
L
8
230VAC 1.5mm²
230VAC 1.5mm²
230VAC 1.5mm²
The main power supply is on the DXA Unit.
Sensors, user’s interface and the exhaust compensation valve are accessed from
communication bus.
Optional exhaust units can be connected to 9 VDC output supply [7] via a 2 wire cable
having a cross sectional area of at least 0.75 mm² and a maximal length of 25 meters.
RJ right plugging
Only RJ12 which the following specifications can used:
24 AWG; CAT5E; straight-thru