Venting and Combustion Air Guide
07/21/11 AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
•
Ph: 800-526-0288 Page
167
of
200
GF-5050
TAG-0043_0C
VENT TERMINATIONS MUST BE AT LEAST
3
FEET
(92
CM
)
ABOVE ANY FORCED AIR
INLET LOCATED WITHIN
10
FEET
(305
CM
).
Figure
8
.
Acceptable Vent Termination Locations
CATEGORY IV VENT TERMINATIONS MUST NOT
TERMINATE OVER PUBLIC WALKWAYS OR OVER
AREAS WHERE CONDENSATE OR VAPOR COULD
CREATE A
NUISANCE OR HAZARD
.
Pg 15 of 22