GF-5030
Gas Supply Design Guide
TABLE 4
Pipe Sizing Table for 5 Pounds Pressure Capacity of Pipes of Different Diameters and Lengths in Cubic
Feet per Hour for an Initial Pressure of 5.0 psi with a 10% Pressure Drop and a Gas of 0.6 Specific Gravity
Pipe Size of
Schedule 40
Standard Pipe
(Inches)
Internal
Diameter
(Inches)
Total Equivalent Length of Pipe (Feet)
50
100
150
200
250
300
400
500
2.00
2.067
11786
8101
6505
5567
4934
4471
3827
3391
2.50
2.469
18785
12911
10368
8874
7865
7126
6099
5405
3.00
3.068
33209
22824
18329
15687
13903
12597
10782
9556
3.50
3.548
48623
33418
26836
22968
20365
18444
15786
13991
4.00
4.026
67736
46555
37385
31997
28358
25694
21991
19490
5.00
5.047
122544
84224
67635
57887
51304
46485
39785
35261
6.00
6.065
198427
136378
109516
93732
83073
75270
64421
57095
Venting of Gas Supply Regulators
AERCO’s general guidelines for venting of gas regulators are listed below. AERCO recommends that
these guidelines be followed to ensure the most reliable and proper operation of AERCO gas fired
equipment. It is also recommended that you consult local codes and the gas regulator manufacturer for
additional details. Always follow the most stringent guidelines available, including those listed below.
•
When venting a gas supply regulator, the vent pipe must be no smaller than the regulator vent size.
•
In a multiple unit installation, each regulator must have a separate vent line.
•
Vent lines must not be manifolded together or with any other equipment at the site that also requires
atmospheric vents.
•
When sizing the vent, pipe diameters must be increased by one pipe diameter every 20 equivalent
feet of pipe.
•
Each 90° elbow is equivalent to approximately:
⇒
2.5 feet for nominal pipe sizes of up to 3/4”
⇒
4.5 feet for nominal pipe sizes of up to 1-1/2”
⇒
10.5 feet for nominal pipe sizes of up to 4”
•
•
Each 45° elbow is equivalent to approximately:
⇒
1 foot for nominal pipe sizes of up to 3/4”
⇒
2 feet for nominal pipe sizes of up to 1-1/2”
⇒
5 feet for nominal pipe sizes of up to 4”
Pg. 7 of 10
Содержание INNOVATION INN1060
Страница 129: ...Appendix H C More Wiring Diagrams Innovation Series Water Heaters USER MANUAL APPENDIX H C MORE WIRING DIAGRAMS ...
Страница 130: ...GF 128 Innovation Series Water Heaters OMM 0079_0B USER MANUAL This Page Is Intentionally Blank ...
Страница 131: ...Appendix H C More Wiring Diagrams Innovation Series Water Heaters USER MANUAL ...
Страница 132: ...GF 128 Innovation Series Water Heaters OMM 0079_0B USER MANUAL This Page Is Intentionally Blank ...
Страница 133: ...Appendix H C More Wiring Diagrams Innovation Series Water Heaters USER MANUAL ...
Страница 134: ...GF 128 Innovation Series Water Heaters OMM 0079_0B USER MANUAL This Page Is Intentionally Blank ...
Страница 135: ...Appendix H C More Wiring Diagrams Innovation Series Water Heaters USER MANUAL ...
Страница 136: ...GF 128 Innovation Series Water Heaters OMM 0079_0B USER MANUAL This Page Is Intentionally Blank ...