Innovation Water Heaters Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0078_0J
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
43
of
196
GF-128
Phone: 800-526-0288
PRI: 11/22/2013
Table 3-4. Configuration Menu - Continued
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (Legacy BMS),
Network
4 – 20 mA,
1-5V
Bldg Ref Temp
(If Mode = Outdoor
Reset)
40°F
230°F
70°F
Reset Ratio
(If Mode = Outdoor
Reset)
0.1
9.9
1.2
Outdoor Sensor
Enabled or Disabled
Disabled
System Start Tmp
(If Outdoor Sensor =
Enabled)
30°F
100°F
60°F
Setpt Lo Limit
40°F
Setpt Hi Limit
60°F
Setpt Hi Limit
Setpt Lo Limit
220°F
140°F
Temp Hi Limit
40°F
240°F
160°F
Max Valve Position
40%
100%
100%
Pump Delay Timer
0 min.
30 min.
0 min.
Aux Start On Dly
0 sec.
120 sec.
0 sec.
Failsafe Mode
Shutdown or Constant Setpt
Shutdown
Low Fire Timer
2 sec.
600 sec.
2 sec.
Setpt Limiting
Enabled or Disabled
Disabled
Setpt Limit Band
0°F
10°F
0
Network Timeout
5 Sec
999 Sec
30 Sec
HI DB Setpt EN
0%
100%
30%
Demand Offsert
0
25
0
Deadband High
0
25
0
Deadband Low
0
25
0
DO NOT CHANGE the Analog Output Menu Item from its Default
setting (Valve Position 0-10V).
3.7 WATER HEATER MANAGEMENT (WHM) MENU
The WHM Menu in each C-More can only be viewed when the
Unit Type
option in the
Configuration Menu is set to
Innovation WH
. Most of the options in this menu are preset at the
factory and cannot be altered by the user. Therefore, the WHM Menu contains only eight (8)
user-selectable menu options. These menu options are listed in Table 3-5. Descriptions for each
of these menu items are included in Appendix A.
*
CAUTION