Innovation Water Heaters Installation, Operation & Maintenance Manual
APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS
OMM-0078_0J
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
123
of
196
GF-128
Phone: 800-526-0288
PRI: 11/22/2013
INNOVATION MENU ITEM DESCRIPTIONS
–
Continued
MENU LEVEL & OPTION
DESCRIPTION
CONFIGURATION MENU
(Cont.)
Demand Offset
This entry will reduce excessive ON/OFF cycling in AUTO
mode. When this entry is a non-zero value, the unit will not
turn on again until
Valve Position In
reaches the Start Level
value AND the Outlet Temperature goes below the
Active
Setpoint – Demand Offset.
In addition, the heater will fire at
the 29% Valve Position level or below for a period of one
minute.
When this entry is set to zero, the unit will turn on again as
soon as the
Valve Position in
reaches the
Start Level
value.
There will not be a one minute delay when firing at the 29%
Valve Position level.
Setting range is 0 to 25. (Default = 0)
Deadband High
Deadband Low
Deadband High and Deadband Low settings create an
“Outlet Temperature” Zone. In which no Valve Position
corrections will be attempted.
The Deadband ZONE is defined as operating with an Outlet
Temperature between Active Se Deadband High and
Active Setpoint – Deadband Low.
When the Outlet Temperature reaches Active Setpoint and
remains there for a period of 15 seconds, the unit will go into
a DEADBAND MODE at which point no Valve Position
corrections will be attempted while the Outlet Temperature
remains anywhere within the Deadband ZONE. When the
unit is in the DEADBAND MODE, the °F or °C LED will flash
on and off. When the Outlet Temperature drifts out of the
Deadband ZONE, the DEADBAND MODE will be terminated
and the PID LOOP will again attempt Valve Position
corrections.
Setting range is 0 to 25.
(Default = 0 for both Deadband High and Deadband Low)