BMK 750-3k Platinum Boiler OPERATION, SERVICE, and MAINTENANCE GUIDE
SECTION 5 – MAINTENANCE
OMM-0116_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
61
of
178
GF-201
Ph.: 800-526-0288
03/15/2017
5.6.1 BMK 750/1000 BURNER INSPECTION
BMK 750/1000 BURNER INSPECTION Instructions
Figure 5-4a: BMK 750/1000 Burner Assembly Mounting Details (Overhead View)
Figure 5-4b: BMK 750/1000 Burner Assembly (Exploded View)
1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power
from the unit and turn off the gas supply.
2. Remove the top shroud from the unit by grasping the top handle and lifting straight up. This
will disengage the shroud from the four (4) pins in the side panels.
AIR/FUEL VALVE
BLOCKED INLET
SWITCH
BURNER GASKET
FLAME DETECTOR
O2 SENSOR
STAGED IGNITION
BURNER
BLOWER
BLOWER PROOF SWITCH
BURNER PLATE
BURNER PLATE
3/16”–16 HEX NUTS (8)
IGNITER-INJECTOR
STAGED IGNITION
ASSEMBLY
BLOCKED INLET
SWITCH
BLOWER PROOF
SWITCH
AIR FILTER
BLOWER
FRONT
1/2" BOLTS & NUTS (4)
(GAS TRAIN-to-A/F
VALVE)
REAR
IGNITER/INJECTOR