![Aerco Benchmark BMK 1000 Скачать руководство пользователя страница 106](http://html.mh-extra.com/html/aerco/benchmark-bmk-1000/benchmark-bmk-1000_operation-and-service-manual_2861518106.webp)
BMK 750-3k Platinum Boiler OPERATION, SERVICE, and MAINTENANCE GUIDE
APPENDIX D – RECOMMENDED PERIODIC TESTING
Page
106
of
178
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0116_0A
03/15/2017
Ph.: 800-526-0288
GF-201
RECOMMENDED PERIODIC TESTING
ITEM
FREQUENCY
ACTION BY
REMARKS
High water temp.
safety control test
Annually
Service Technician
See section 5.5 in the
Benchmark 750 – 3000
Installation and Startup Guide
, OMM-0115
(GF-200).
Operating controls
Annually
Operator
See section 2.2.
Low air flow
Monthly
Operator
See section 5.8 in the
Benchmark 750 – 3000
Installation and Startup Guide
, OMM-0115
(GF-200).
High and low gas
pressure interlocks
Monthly
Operator
See sections 5.2 and 5.3 in the
Benchmark
750 – 3000 Installation and Startup Guide
,
OMM-0115 (GF-200)
Air/Fuel Valve purge
position switch
Annually
Service Technician
See section 5.10 in the
Benchmark 750 –
3000 Installation and Startup Guide
, OMM-
0115 (GF-200)
Air/Fuel Valve
ignition position
switch
Annually
Service Technician
See section 5.11 in the
Benchmark 750 –
3000 Installation and Startup Guide
, OMM-
0115 (GF-200)
Safety valves
As required
Operator
Check per A.S.M.E. Boiler and Pressure
Vessel Code, Section IV.
Inspect burner
components
Semi-Annually
Service Technician
See section 5.6.
Condensate Trap
Semi-
Annually
Operator
See section 5.8.
Oxygen (O
2
) Level
Monthly
Operator
Verify oxygen level is between 3% and 8%
during boiler operation.