BMK 750-3k Platinum Boiler OPERATION, SERVICE, and MAINTENANCE GUIDE
SECTION 5 – MAINTENANCE
Page
56
of
178
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0116_0A
03/15/2017
Ph.: 800-526-0288
GF-201
The igniter-injector may be hot, therefore, care should be exercised to avoid burns. It is easier to
remove the igniter-injector from the unit after the unit has cooled to room temperature. To
inspect/replace the Igniter:
IGNITER-INJECTOR MAINTENANCE PROCEDURE Instructions
1. Set the ON/OFF switch on the control panel to the
OFF
position. Disconnect AC power
from the unit
2. Remove the top shroud from the unit by grasping the top handle and lifting straight up. This
will disengage the shroud from the four (4) pins in the side panels.
3. Disconnect the cable from the igniter-injector (see Figure 5-1a – Figure 5.1c, above).
4. Referring to Figure 5-2a – Figure 5.2c, below, use a 7/16” open-end wrench to disconnect
the compression nut securing the gas injector tube of the igniter-injector to the elbow of the
staged ignition assembly. Disconnect the staged ignition assembly from the igniter-injector.
Figure 5-2a: BMK 750/1000 Igniter-Injector & Flame Detector Mounting Details
Figure 5-2b: BMK 1500/2000 Igniter-Injector & Flame Detector Mounting Details
LEAN O
2
SENSOR
& WASHER
STAGED
IGNITION
SOLENOID
IGNITER-INJECTOR
INDEXING
(CLOCKING)
WASHERS
(0-3 as required)
FLAME
DETECTOR
& GASKET
BURNER
PLATE
STAGED
IGNITION
SOLENOID
FLAME
DETECTOR &
GASKET
FLAME
OBSERVATION
PORT
INJECTOR-IGNITER
ASSY WITH INDEXING
(CLOCKING) WASHERS
(0-3 as needed)
LEAN O2 SENSOR
& WASHER
BURNER PLATE
FLANGE
BLOWER
PLENUM
COMPRESSION
FITTING & ELBOW