OMD94016 REV.
C
53
Alarm
A41 RECT ERROR LOOP
Description
The control is not able to regulate the rectifier output
voltage precisely.
Possible
causes
•
Regulation system failure.
Solutions
1) Reset the system.
2) If the alarm persists, contact our Technical Support
Service.
Alarm
A43 CURR ERROR LOOP
Description
The control is not able to regulate the rectifier output
current precisely.
Possible
causes
•
Regulation system failure.
Solutions
1) Reset the system.
2) If the alarm persists, contact our Technical Support
Service.
Alarm
A46 PAR LOST REDUND
Description
This alarm is only active on PARALLEL systems.
Continuity is not ensured in the event of a fault on one of
the UPS units.
Possible
causes
•
The total load is higher than the maximum expected
value.
•
Possible failure on the measuring circuit.
Solutions
1) Check the load fed by the system.
2) If the alarm persists, contact our Technical Support
Service.
Alarm
A47 SEND PARAM ERROR
Description Internal error
Possible
causes
•
Micro-controller communication problems.
Solutions
1) Contact our Technical Support Service.