OMD94016 REV.
C
39
In case there are more than four paralleled devices, the menu will be as
follows.
PARALLEL
1- S
2- M
3- [ S ]
. . . .
The dots indicate the presence of a further menu which shows the status
of the other UPS units in the system.
7.1.4
PARALLEL TYPE
PARALLEL
REx
The string on the second line may have two values, “POWER” or
“REx”.
•
POWER means that the parallel system is set so as to require the
presence of all the UPS units in order to feed the load.
•
REx means that the system is redundant and the
redundancy index is indicated by number “X”. For example, in a
system composed of 3 UPS units, “RE2means that only
one of the UPS units is sufficient to feed the load.
7.1.5
MESSAGE STATISTICS
The statistics section regarding the messages exchanged on the
communication buses consists of three different menus.
STATIST CAN SSW
MSG RX: 32564 100.0%
Number of messages received and percentage of reception accuracy
regarding the status of the static switches. The messages are
exchanged between all the UPS units, therefore the number will increase
on all of them.
STATIST CAN INV
SYNC RX: 15849 100.0%