OMD94016 REV.
C
31
6.2
DISPLAY LANGUAGE SETTING
The table below shows the languages which can be set for the display.
Parameter
Standard
Range
LANGUAGE
ITALIAN
ITALIAN
GERMAN
FRENCH
ENGLISH
PORTUGUESE
SPANISH
POLISH
TURKISH
The parameters are changed via the arrow buttons (
/
) to
increase the digits, and the
button is used to confirm the entry.
6.3
NEW BATTERY INSTALLATION
The NEW BATTERY INSTALLATION menu is used in case the battery
circuit breaker BCB is not closed, when requested, in the start-up phase.
In this case the system will start considering the battery completely
discharged and activating the alarm “A10 – BATTERY FAULT”.
To set the battery autonomy to 100% it is necessary to access the menu
and press the
button to confirm.
6.4
BATTERY CONFIGURATION
In case the UPS has been tested without knowing the characteristic data
of the storage battery, the BATTERY CONFIGURATION menu allows for
the setting of such data. In particular, the following data can be set:
•
Battery capacity in Ampere-hours (Ah)
•
Recharging current in Amperes (A)
•
Nominal autonomy in minutes