Technical Data
Operations Manual Thyro Power Manager
Page 26 of 26
Version: 1.7.2009
8000022632 BAL, EN
tapping 7
190V~
stage 1
General:
Type voltage
230V~
-15% / +10%
The Unit corresponds to:
DIN EN 50178
(see Operations Manual Thyro-A)
Mains frequency:
47 – 63 Hz
Operating mode:
Continuous and contactless stage change-over of the
transformer tappings
Stage setting:
Two binary control inputs, possibly
connected to a timer
or via bus system
Control of:
voltage
Protection class:
IP00
Ambient temperature:
-10° C to +45 °C
Load types:
Ohm inductive load types, compensated or uncompensated
lamps, cos phi 1 - 0.1 e.g. sodium vapour lamps (NAV), mercury
vapour lamps (HQL), fluorescent tubes (TL), halogen lamps or
simple incandescent lamps.
Monitoring systems:
Undervoltage
Overvoltage
Temperature of the unit
Mains frequency
Lamp current
Times in the power controller:
Warm-up time after reset (Unit on)
Warm-up time after control signal
Waiting time under-/overvoltage
default = 5min
default = 5min
default = 5min
Timer:
With calendar, automatic change between daylight saving time
and winter time
Power reserve: 5 years
Day and week programme
etc.
Analogue output:
Output potential of:
lamp voltage, lamp current, lamp power, etc.
signal level 0 - 10 volt, 0 - 20 mA, 4 - 20 mA selectable
Relay output:
Change-over contact, max. 250V, 6A, 180W, 1500VA